3.11

Gas side pressure drops

Gas pressure on the basis of the maximum output developed by
the burner is given by the curves in Fig. 6.
It represents the pressure drop in the combustion head.
Natural gas G 20 - N.C.V. = 10 kWh/Nm
The curves were taken in the following conditions:
pressure measured at the test point on the pressure switch
downstream from the gas butterfly valve;
combustion chamber at 0 mbar;
burner working at full output.
Combustion head pressure drop
Butterfly valve pressure drop
Technical description of the burner
3
70
65
60
55
50
45
40
35
30
25
20
15
10
5
0
2000
4000
6000
8000
Pb (burner output)
26
24
22
20
18
16
14
12
10
8
6
4
2
0
0
2000
4000
6000
8000
Pb (burner output)
Add the pressure of the combustion chamber in
mbar to the value of the combustion head drop.
WARNING
The pressure drop of the completely open butterfly valve is given
in Fig. 7.
10000
12000 14000
16000 18000
[kW]
G25
(DB16)
G20
(DB16)
G31
(DB16)
10000
12000 14000
16000 18000
[kW]
11
GB
G31
G25
G20
20000
22000
D3891
G25
(DB20)
G20
(DB20)
G31
(DB20)
20000
22000
Fig. 6
Fig. 7
20155221