Gas Side Pressure Drop - Riello DB 6 LSE C13 Installation, Use And Maintenance Instructions

Light oil/gas dual fuel industrial burners
Table of Contents

Advertisement

2.6

Gas side pressure drop

80
70
60
50
40
mbar
30
20
10
0
Fig. 8
20
18
16
14
12
10
8
mbar
6
4
2
0
Fig. 9
8
1000
2000
4000
Pb (Burner output)
Butterfly valve pressure drop
1000
2000
4000
Pb (Burner output)
2
CHAPTER
Head pressure drop
D8327
6000
8000
[kW]
D8328
6000
8000
[kW]
Burner description
Gas pressure on the basis of the
maximum output developed by
the burner is given by the curves
in Fig. 8.
It represents the pressure drop
in the combustion head.
Natural gas G 20 - Net calorific
3
value = 10 kWh/Nm
The curves were taken in the fol-
lowing conditions:
• pressure measured at the test
point on the pressure switch
downstream from the gas but-
terfly valve;
• combustion chamber at 0
mbar;
KW
• burner working at full output.
The pressure drop of the com-
pletely open butterfly valve is
given in Fig. 9.