Sensor replacement
▪ the calibration certificate of the sensor:
▪ the additional nameplate of the sensor:
There are two possibilities to configure the transmitter with all relevant settings to ensure
Communication
a possibilities proper operation:
possibilities
▪ Parameter setting via communication tool like 475 Configurator or DTM
▪ Parameter setting via transmitter display, if available

18.3.2 Parameter setting procedure

The coupling of the existing transmitter with the spare sensor can be executed with the
following procedure:
1. Set the process parameter units to standard units.
2. Copy and rename the file "Factory.PAR", available on the delivered microSD card, to
The use of the microSD card is possible only for transmitters with display
(indicated on order code position 16 = 3)
3. Run the function "Download sensor constants from microSD card". Please refer to

18.4 Wiring

For the wiring of Spare sensor and existing transmitter, please refer to chapter Wiring
[} 105].

18.5 Commissioning

1. Activate external power switch.
2. Perform check of piping installation.
3. Check flow meter for device errors, warnings or alarms,
4. Configure the transmitter, and perform autozero,
ð Flow meter is ready for operation.
154 / 180
35
16.8
144
Please refer to chapter Set up process variable units.
the microSD card of the existing transmitter.
chapter Set up sensor relevant and sensor specific parameters [} 162].
see chapter Troubleshooting.
see chapter System configuration and operation.
A5E52748387-AA, 2023/09