CyberPower OLS6KERT4UA Installation And Operation Manual page 31

Table of Contents

Advertisement

Setting Item &
LCD Display
Cold Start
C19 Cold Start
Automatic Restore
C20 Auto Restore
Minimum Restored
Capacity
C21 Min. Restore%
Charging Current
C22 CHGR Current
EBM Number
C25 EBM Number
Battery Replace Date
C26 Replace Batt
Period Battery Test
C27 PD. BattTest
USING THE UPS SYSTEM
Available Settings
(* = default setting)
[Disable], [Enable]*
[Disable], [Enable]*
[0%]*, [15%], [30%], [45%], [60%],
[75%], [90%]
[1A]*, [2A], [3A], [4A]
[Autodetect]*, [0-10 pack(s)]
[Clear], [----/--/--]
[Disable]*, [1 Week], [2 Weeks], [3
Weeks], [4 Weeks]
The UPS can start without utility when
this is [Enable].
User can [Disable] or [Enable] the
automatic restore function. If selecting
[Enable] (default), the UPS will restart
automatically when input power is
restored after a complete shutdown
when battery is end of discharge.
When the utility power restores, the UPS
will start to recharge until the selected
battery capacity is met before restoring
output power.
Sets the maximum charging current for
the battery.
NOTE: The available setting of charging
current is based on the quantity of
the Extended Battery Module (EBM).
Please refer to Chapter [ELECTRICAL
INSTALLATION-CHARGING CURRENT
SETTING GUIDE] for details.
Sets the number of attached external
battery module(s) or allows the number
of external battery module(s) with
autodetect. Autodetect is used only for
CyberPower EBMs. If more than 3 EBMs
are connected, auto-detection does not
funtion.
An optional setup item for users to
record the installation date of the battery
pack. Reset the date when replacing new
battery pack.
The UPS can periodically self-test the
battery. Sets periodic test for battery.
29