CyberPower OLS6KERT4UA Installation And Operation Manual page 30

Table of Contents

Advertisement

Setting Item &
LCD Display
Signal Inputs
C12 Signal Input
Audible Alarm
C13 Audible Alarm
Screen Saver
C14 Screen Saver
Dry Relay Function
C15 Dry Relay
Reset Load Energy
C16 Reset Load
Clear Event Log
C17 CLR Event Log
Date & Time
C18 Date&Time
USING THE UPS SYSTEM
Available Settings
(* = default setting)
[Disable]*, [EPO], [ROO]
[Disable], [Enable]*, [Muted]
[Disable], [1 Minute], [5 Minutes]*
[I/P Power Fail], [Battery Low],
[UPS On Bypass], [UPS Fail]*,
[Summary Alarm]
[Clear]
[Activate?]
----/--/--, --:--:--
(year/month/day, hr:min:sec)
Sets [EPO] (Emergency Power Off) to
shutdown the UPS remotely when the
contact is close.
Sets [ROO] (Remote On/Off) to turn
On the UPS remotely when the contact
is close and turn Off the UPS remotely
when the contact is open. The On/Off
power button on front panel will be
disabled when set to [ROO].
User can [Disable] or [Enable] the
buzzer sound or enable buzzer when
battery low.
Sets the amount of time of the LCD
screen OFF after no user input. The
[Disable] option keeps the LCD screen
on at all times.
Sets the output of dry contact.
Reset Load Energy Consumption (KWH)
value.
Clears all the events stored in the EVENT
LOGS of LCD Control Panel.
Sets Year/Month/Day Hour: Minute:
Second to UPS. Or get Date & Time from
PPBE (Agent) or RMCARD automatically.
28
Description

Advertisement