CyberPower OLS6KERT4UA Installation And Operation Manual page 29

Table of Contents

Advertisement

Setting Item &
LCD Display
Manual Bypass
C06 Manual Bypass
ECO Mode
C07 ECO Mode
ECO Voltage Range
C08 ECO V Range
ECO Frequency Range
C09 ECO Freq.
Generator Mode
C10 Generator
Converter Mode
C11 Converter
USING THE UPS SYSTEM
Available Settings
(* = default setting)
[Disable]*, [Enable]
[Disable]*, [Enable]
[10%]*, [15%]
[±1%], [±2%], [±3%], [±4%],
[±5%]*, [±6%], [±7%], [±8%]
[Disable]*, [Enable]
[Disable]*, [Output Freq= 50Hz],
[Output Freq = 60Hz]
When performing UPS maintenance, user
can manually transfer the connected load
to Bypass without interrupting the output
to the connected equipment.
Sets the ECO operation for the UPS.
NOTE: This function can't be set when
Manual Bypass, Generator Mode or
Converter Mode is enabled.
Sets the percentage that the input
voltage may be above or below the
selected output voltage setting and
remain in ECO mode.
Sets the percentage that the input
frequency may be above or below the
selected frequency setting and remain
in ECO mode.
When the UPS input power source is a
generator, the UPS will operate normally
without transferring to Battery Mode
when this is [Enable].
NOTE: Enabling ""Generator Mode""
allows the UPS to accept a wider voltage
range and frequency variation than it
would normally accept when plugged
into a wall socket on utility.
Selects the frequency of the output.
NOTE: UPS has no bypass when
Converter Mode is enabled. This function
can only be set before turn on the UPS.