Configuration
STEP 3
Discharge Air Economizer: Select the discharge air setpoint.
STEP 4
Discharge Air Low Limit: Select the discharge air low limit
value.
STEP 5
Economizer Proportional Band: Set the discharge air
proportional band or throttling range.
STEP 6
Outdoor Air Damper Minimum Position: Set the minimum
damper position.
STEP 7
Economizer Output: Select whether the modulating output
range will be 0 – 20mA or 4 – mA.
STEP 8
Economizer Control Action: Select whether the economizer
control action will direct- or reverse-acting.

Digital Inputs

STEP 1
DI1: Select either FAN PROVING or MONITOR. If DI1 is unused,
select MONITOR.
STEP 2
DI2: Select SERVICE, ECON or MONITOR. If DI2 is unused,
select MONITOR.
STEP 3
DI2 Setpoint Shift: Enter the setpoint shift value.
NOTE:
This screen will only appear if DI2 is set to Monitor
(see Step 2).
STEP 4
DI3: Select FILTER, SERVICE, EXTERNAL OVERRIDE, or
EXTERNAL TIMECLOCK. If DI3 is unused, select EXTERNAL
OVERRIDE.
9
9
2800 Laura Lane
Middleton, WI 53562
DSCHARGE AIR ECON
SETPOINT:
DSCHARGE AIR ECON
LOW LIMIT:
DSCHARGE AIR ECON
PROP BAND:
OUTDOOR DAMPER
MIN POSITION:
ECON OUTPUT
RANGE:
ECON CONTROL
ACTION:
DI1 USED FOR
DI2 USED FOR
DI2 SETPOINT
SHIFT
DI3 USED FOR:
FILTER SERVICE
|
800.288.9383
|
www.tcsbasys.com
055F
040F
010F
10%
4-20MA
DIRECT
MONITOR
MONITOR
00F