Configuration
STEP 21 Outdoor Air Sensor Function: Select whether you are using
an outdoor air sensor. To monitor only, select NO.
NOTE:
Refer to the
Manual
for dip switch settings, which must also be set
STEP 22 Cooling Lockout: Enter an outdoor air cooling lockout
temperature.
NOTE:
This screen appears only if the discharge air sensor
function is enabled (Step 21).
STEP 23 Heating Lockout: Enter an outdoor air heating lockout
temperature.
NOTE:
This screen appears only if the discharge air sensor
function is enabled (Step 21).
Digital Inputs
STEP 1
DI1: Select either FAN PROVING or MONITOR. If DI1 is unused,
select MONITOR.
STEP 2
DI2: Select SERVICE, AQUASTAT, or MONITOR. If DI2 is
unused, select MONITOR.
STEP 3
DI2 Setpoint Shift: Enter the setpoint shift value.
NOTE:
This screen will only appear if DI2 is set to Monitor
(Step 2).
STEP 4
DI3: Select FILTER, SERVICE, EXTERNAL OVERRIDE, or
EXTERNAL TIMECLOCK. If DI3 is unused, select EXTERNAL
OVERRIDE.
Energy Saving
STEP 1
Delay on Powerup: In the event of a power interruption,
entering a value (in seconds) that will delay the powerup of the
SuperSTAT.
STEP 2
Smart Recovery: Select whether to use Smart Recovery
Mode.
NOTE:
Smart Recovery is not available when DI3 (see
Inputs: STEP 4" on page
time clock.
10
SZ1051/1053 SuperSTAT Installation
10) is configured for an external
2800 Laura Lane
•
Middleton, WI 53562
ENABLE OUTDOOR
AIR FUNCT?
COOLING LOCKOUT
TEMP
HEATING LOCKOUT
TEMP
DI1 USED FOR
DI2 USED FOR
SET DI2 SETPOINT
SHIFT:
DI3 USED FOR:
FILTER SERVICE
DELAY ON POWERUP
ENABLE SMART
"Digital
RECOVERY?
|
800.288.9383
|
www.tcsbasys.com
YES
60F
70F
MONITOR
MONITOR
00F
010 SECONDS
NO