Digital Inputs; Energy Saving - TCS SuperSTAT SZ1053 Configuration Manual

Communicating thermostat
Hide thumbs Also See for SuperSTAT SZ1053:
Table of Contents

Advertisement

Configuration
STEP 21 Outdoor Air Sensor Function: Select whether you are using
an outdoor air sensor. To monitor only, select NO.
NOTE:
Refer to the
Manual
for dip switch settings, which must also be set
STEP 22 Cooling Lockout: Enter an outdoor air cooling lockout
temperature.
NOTE:
This screen appears only if the discharge air sensor
function is enabled (Step 21).
STEP 23 Heating Lockout: Enter an outdoor air heating lockout
temperature.
NOTE:
This screen appears only if the discharge air sensor
function is enabled (Step 21).

Digital Inputs

STEP 1
DI1: Select either FAN PROVING or MONITOR. If DI1 is unused,
select MONITOR.
STEP 2
DI2: Select SERVICE, AQUASTAT, or MONITOR. If DI2 is
unused, select MONITOR.
STEP 3
DI2 Setpoint Shift: Enter the setpoint shift value.
NOTE:
This screen will only appear if DI2 is set to Monitor
(Step 2).
STEP 4
DI3: Select FILTER, SERVICE, EXTERNAL OVERRIDE, or
EXTERNAL TIMECLOCK. If DI3 is unused, select EXTERNAL
OVERRIDE.

Energy Saving

STEP 1
Delay on Powerup: In the event of a power interruption,
entering a value (in seconds) that will delay the powerup of the
SuperSTAT.
STEP 2
Smart Recovery: Select whether to use Smart Recovery
Mode.
NOTE:
Smart Recovery is not available when DI3 (see
Inputs: STEP 4" on page
time clock.
10
SZ1051/1053 SuperSTAT Installation
10) is configured for an external
2800 Laura Lane
Middleton, WI 53562
ENABLE OUTDOOR
AIR FUNCT?
COOLING LOCKOUT
TEMP
HEATING LOCKOUT
TEMP
DI1 USED FOR
DI2 USED FOR
SET DI2 SETPOINT
SHIFT:
DI3 USED FOR:
FILTER SERVICE
DELAY ON POWERUP
ENABLE SMART
"Digital
RECOVERY?
|
800.288.9383
|
www.tcsbasys.com
YES
60F
70F
MONITOR
MONITOR
00F
010 SECONDS
NO