Installation

Temperature Inputs

Connect 1000Ω PtRTD temperature sensor inputs (range of –40ºF to 160ºF) using 18AWG two-wire twisted, stranded
shielded wire, maximum 250 ft. length. Sensors can be used for remote zone temperature, return air temperature,
discharge air temperature, or outside air temperature. Sensor wires should be kept at least five feet from live voltage
wiring.
NOTE:
When using remote sensors, the unit may need to be calibrated See the
or the
SZ1053 SuperSTAT Configuration Guide
R W/Y1 W/Y2 G
Y2
+
24V
DI1
DI2
DI3 OVR T1

Digital Inputs

Digital inputs are used to receive status signals such as filter status, fan status, etc. Use unpowered dry contacts only with
18AWG two-wire twisted, stranded shielded or unshielded wire.
R W/Y1 W/Y2 G
Y2
+
24V
DI1
DI2
DI3 OVR T1
7
7
for more information.