Digital Inputs; Temperature Inputs; Analog Inputs - TCS UbiquiSTAT US4050 Installation Manual

Commercial bacnet controller
Hide thumbs Also See for UbiquiSTAT US4050:
Table of Contents

Advertisement

Installation

Digital Inputs

Digital inputs are used to receive status signals such as filter status, fan status, etc. Use unpowered dry contacts only with
18AWG two-wire twisted, stranded shielded or unshielded wire.
R
W1 W2
Y1
Y2
G
B/O
TC
AO1 AO2 GND
A
B
REF
+
24V
DI1
DI2
DI3 GND
T1
T2
T3
+P AI1
AI2 GND
'10
'20
'40

Temperature Inputs

Connect 1000Ω PtRTD temperature sensor inputs (range of -40ºF to 160ºF) using 18AWG two-wire twisted, stranded
shielded wire, maximum 250 ft. length. Sensors can be used for remote room temperature, discharge air temperature,
outdoor air temperature or mixed air temperature. Sensor wires should be kept at least five feet from live voltage wiring.
NOTE:
When using remote sensors, the unit may need to be calibrated See the
information.
R
W1 W2
Y1
Y2
G
B/O
TC
AO1 AO2 GND
A
B
REF
+
24V
DI1
DI2
DI3 GND
T1
T2
T3
+P AI1
AI2 GND
'10
'20
'40

Analog Inputs

Connect 0 – 20mA or 4 – 20mA analog inputs using 18AWG two-wire twisted, stranded shielded wire. These inputs can
be used for any current-based sensors such as CO
R
W1 W2
Y1
Y2
G
B/O
TC
AO1 AO2 GND
A
B
REF
+
24V
DI1
DI2
DI3 GND
T1
T2
T3
+P AI1
AI2
GND
7 7
'50
'50
and humidity. Inputs can be two-wire or self-powered.