GEM 533 eSyStep Operating Instructions Manual page 19

Motorized globe valve
Table of Contents

Advertisement

8.3 Overview of available functions – Input and output signals
▶ The factory default setting "Configured for emergency power supply module" is reset to default settings when a reset is car-
ried out.
▶ When the digital inputs for OPEN and CLOSE are activated simultaneously, the defined error position is approached.
Digital input 1
Digital input 2
Digital input/output
Digital output
Analogue input
Analogue output
www.gemu-group.com
Function
Off/Open/Closed/Safe/On/Ini-
tialization
Off/Open/Closed/Safe/On/Ini-
tialization
Open/Closed/Error/Error and
warning/Initialization
Open/Closed/Error/Error and
warning
4–20 mA/0–20 mA/0–10 V
4–20 mA/0–20 mA/0–10 V
NOTICE
NOTICE
Control module S0
Default settings
Initialization
Off
Error
Closed
4–20 mA
4–20 mA
19 / 64
8 Electrical connection
Control module S5, S6
Factory default setting "Con-
figured for emergency power
supply module"
Initialization
Safe/On
Error
Closed
4–20 mA
4–20 mA
GEMÜ 533 eSyStep
Positioner (Code S0)

Advertisement

Table of Contents