3.1 Setting of Purpose and Communication Conditions

3.1 Setting of Purpose and Communication Conditions

3.1.1 Purpose to be Set for Each Port

List of available functions by communication port (●: Available; ○: Conditionally
available; Blank: Not available)
Available communication functions
PLC link
MEWTOCOL-COM
(Note 3)
MODBUS-RTU
General-purpose communication
(Note 1)
For PLC link, only one port may be used (either COM0 port that is built in the Control Unit as standard
equipment, or COM1 port on a cassette).
(Note 2)
The COM4 port supports only MEWTOCOL-COM communication. In addition, the communication
parameters (unit number, communication format, baud rate) when the power is ON are the same as
the settings of the COM3 port. After RUN, you can also change the conditions by the SYS1 instruction.
(Note 3)
The AFPX-COM5 Cassette (Ethernet type) does not support MODBUS-RTU (master / slave).

3.1.2 Communication Conditions to be Set for Each Port

Communication conditions that can be set vary by the mode to be used.
Communication conditions
Communication port
Unit number
Communication mode
Baud rate
Data length
Parity
Transmission
Stop bit
format
Terminator
3-2
Control
Unit
COM0
Master
Slave
Master
Slave
Setting range
1 to 99
Computer link, general-purpose
communication
PLC link, MODBUS RTU
2400, 4800, 9600, 19200,
38400, 57600, 115200, 230400
7 bits, 8 bits
None, Odd, Even
1 bit, 2 bits
CR, CR+LF, ETX, time
Terminator judgment time
Allocated communication port No.
Cassette mounting
part 1
COM1
COM2
Default
1
Computer link
9600
8 bits
Odd
1 bit
CR
(Note 3)
WUME-FPXHCOMG-02
Cassette mounting
part 2
COM3
COM4
Remarks