10.3 MODBUS RTU Format

10.3 MODBUS RTU Format

10.3.1 MODBUS RTU Command Format

MODBUS RTU Command Format

START
3.5-character
time
ADDRESS (Unit
No.):
FUNCTION:
DATA:
CRC:
END:
Reception judgment time
The process for receiving a message completes when the time that is exceeding the time
mentioned below has passed after the final data was received. Reception done judgment time
is time for approx. 32 bits.
Baud rate Reception done judgment time
300
Approx. 106.7 ms
600
Approx. 53.3 ms
1200
Approx. 26.7 ms
2400
Approx. 13.3 ms
4800
Approx. 6.7 ms
9600
Approx. 3.3 ms
19200
Approx. 1.7 ms
38400
Approx. 0.8 ms
57600
Approx. 0.6 ms
115200
Approx. 0.3 ms
230400
Approx. 0.14 ms

10.3.2 MODBUS RTU Response Format

Response in normal status
● The same message as a command is returned for a single write command or for a loop back
test.
● A part of a command message (6 bytes from the beginning) is returned for multiple write
command.
10-8
ADDRESS
FUNCTION
8 bits
8 bits
8 bits, 0 to 247 (decimal)
Note) 0 = Broadcast address
8 bits
Varies depending on commands.
16 bits
3.5-character time (Varies by baud rate. Refer to reception judgment time.)
DATA
CRC CHECK
n*8 bits
16 bits
END
3.5-Character
time
WUME-FPXHCOMG-02