Siemens SITRANS L Operating Instructions Manual page 90

Radar transmitters
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

more detailed error messages available under the menu item " Diagnostics" via the
respective adjustment module.
Status messages
The status messages are divided into the following categories:
and explained by pictographs:
1
2
3
4
Figure 12.1
Malfunction (Failure):
Due to a malfunction in the transmitter, a fault signal is output.
This status message is always active. It cannot be deactivated by the user.
Function check:
The transmitter is being worked on, the measured value is temporarily invalid (for
example during simulation).
This status message is inactive by default.
Out of specification:
The measured value is unreliable because an transmitter specification was exceeded
(e.g. electronics temperature).
This status message is inactive by default.
Maintenance required:
Due to external influences, the transmitter function is limited. The measurement is
affected, but the measured value is still valid. Plan in maintenance for the transmitter
because a failure is expected in the near future (e.g. due to buildup).
This status message is inactive by default.
SITRANS LR150
Operating Instructions, 10/2022, 62711-76-01, A5E50352155
Failure
Function check
Out of specification
Maintenance required
Failure - red
Out of specification - yellow
Function check - orange
Maintenance required - blue
Pictographs of the status messages
Diagnostics and troubleshooting
12.4 Status messages according to NE 107
81

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lr150

Table of Contents