Setup with the integrated HMI
7.7.2 Transmitter
Linearization type
Sets the type of linearization to calculate the volume or volume flow.
7.7.2
Transmitter
Units
Sets the measuring unit used.
Setting
Transmitter
7.7.3
Adjustment
Lower calibration point
LOWER CAL POINT:
Sets the distance from the transmitter reference point to the lower calibration point.
Upper calibration point
UPPER CAL POINT:
Sets the distance from the transmitter reference point to the upper calibration point.
Transmitter offset
SENSOR OFFSET:
Sets an offset to compensate for changes in the transmitter reference point.
Changes in the transmitter reference point can be caused, for example, by using a
thicker seal or reducing the height of the mounting nozzle.
50
Selection
Selection
UNITS
mm
m
in
ft
Description
Millimetre
Meter
Inch
Feet
Operating Instructions, 10/2022, 62711-76-01, A5E50352155
SITRANS LR150