Specifications
DC Output
DC current capacity (I
)
MP
Voltage
+3.3 V
+5 V
+12 V
-12 V
5 VAUX
Maximum total available power for the NI PXIe-1085 12 GB/s is 791 W.
Note
Maximum total available power for the NI PXIe-1085 24 GB/s is 775 W.
Backplane slot current capacity
Slot
System Controller Slot
System Timing Slot
Hybrid Peripheral Slot with
PXI-1 Peripheral
Hybrid Peripheral Slot with
PXI-5 Peripheral
PXI-1 Peripheral Slot
Total system slot current should not exceed 45 A.
Notes
PCI V(I/O) pins in PXI-1 peripheral slots and hybrid peripheral slots are connected
to +5 V.
The maximum power dissipated in the system slot should not exceed 140 W.
The maximum power dissipated in a peripheral slot should not exceed 38.25 W.
A-2 | ni.com
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Maximum Current
NI PXIe-1085 12 GB/s
60 A
44 A
62 A
4 A
2 A
+5 V
V(I/O)
+3.3 V
+12 V
15 A
15 A
30 A
6 A
4 A
6 A
5 A
6 A
1 A
6 A
4 A
6 A
11 A
6 A
1 A
NI PXIe-1085 24 GB/s
60 A
49 A
62 A
4 A
2 A
-12 V
5 VAUX
1 A
1 A
1 A
1 A
1 A