• 1:N NT Links
Item
Communications standards
Connectors
Number of Units connected
Transmission distance
Note 1. When using an NS-AL002 Adapter, the transmission distance is as follows:
RS-422A cable: Up to 500 m total extended length.
2. The NS-AL002 is required when connecting two or more PTs to the host.
RS-422A cable: Up to 500 m total extended length.
• Bar Code Reader
Item
Communications
Conforms to EIA RS-232C.
standards
Communications
Start-stop synchronization
settings
Baud rate: 4,800, 9,600, or 19,200 bps
Data length: 7 or 8 bits
Stop bits: 1 or 2 bits
Parity: None, odd, or even
Flow control: RS/CS control
Ports that can be
Either port A or port B only.
connected
Number of Units
1:1
connected
Transmission dis-
Using PT serial port and D-Sub 6-pin Using external power supply
tance
2 m
Communications
No protocol mode
protocol
Data format
[STX]
Power supply
Using PT serial port and D-Sub 6-pin Using external power supply
5 V ±5% 250 mA max.
● Ethernet Specifications (NS15-TX01@-V2, NS12-TS01(B)-V1, NS10-
TV01(B)-V1, NS8-TV@1(B)-V1, NS5-SQ01(B)-V1, NS5-SQ@1(B)-V2, NS5-
TQ@1(B)-V2, NS5-MQ@1(B)-V2)
Item
Conformance standards
Conforms to IEEE 802.3 / Ethernet (10/100Base-T).
Transmission medium
2 pair Cat 3 UTP 22 to 26AWG, Cat 5, Cat 5e, Cat 6
Transmission distance
100 m (node-to-hub and hub-to-hub)
Connector
8-pin modular connector
Specifications
Conforms to EIA RS-232C.
D-Sub female 9-pin connector
(Serial ports A and B)
1:1 to 8
Up to 15 m. (See note 2.)
Specifications
15 m