• The minimum length of the communications cable between nodes is 1 m.
Precautions
Prepare the communications cables at a length of 1 m or longer.
for Safe Use
• Use the multidrop method for connecting nodes. Normal communications
will not be possible with T branches.
Ground all of the shield lines (including the shield line for the node at only one end of the
network) in the way shown below.
Board at the end of
the network
Terminating
resistance: ON
Ground
Reference •
Terminals of the same type are connected internally. They can thus be connected to
either the right or left half of the end Boards.
Connecting Cables to Communications Connectors
When connecting a communications cable to a Controller Link Support Board, connect the
cable to the attached connector first and then attach to the connector to the Board.
Connect the communications cable to the connector using the following procedure.
1. Taking care not to damage the mesh of the shield, strip about 50 mm off the end of the
cable. Do not strip the cable too far because it may cause a short-circuit.
Approx. 50 mm
3-8 Installing the Controller Link Interface Unit
Board in the middle
of the network
Terminating
resistance: OFF
End Board
Board at the end of
the network
Terminating
resistance: ON
3-55