Engine driven generator sets
Table of Contents

Advertisement

OM-2032 / Operation and Maintenance Manual
100D20 / Generator Sets
(2) Tray installation
a. Use both hands to support tray as in removal above.
b. Align rails (4) with tracks (5) and slide tray into box. Latches will lock automatically.
c. Connect Amphenol Connector (3) .
c. Generator Exciter
Provisions have been made to allow removal of the generator exciter without disturbing or
removing the complete generator.
(1) Preparation for exciter removal.
Remove front access panel to remove generator exciter.
(2) Exciter removal:
Refer to TM-360 in Chapter 6 for exciter instructions.
(3) Exciter installation:
a. Install exciter in accordance with TM-360.
b. Reinstall front access panel.
d. Engine Control Panel
The engine control panel is designed and mounted so that it may be released and tilted outward for
access to components on the back side (see Fig. 7) .
(1) Tilt out engine control panel
a. Remove clamp screw which supports wire conduit above output terminal panel.
b. Remove two cap screws which attach engine control panel to frame of control box.
c. Maneuver panel to tilt it inward at the bottom and outward at the top.
March 31/94 Revised
1. Latch
2. Fastener
3. Connector
4. Rail
5. Track
Typical Tray Removal