Note the following:
1. The supply air CFM must be within the limitations
shown in the Unit Application Data Table 1.
2. Pulleys can be adjusted in half turn increments.
3. The tension on the belt should be adjusted as
shown in the Belt Adjustment Figure 20.
4. Tighten blower pulley and motor sheave set screws
after any adjustments. Re-check set screws after
10-12 hrs. run time is recommended.
FIGURE 20 - BELT ADJUSTMENT

AIR BALANCE

Start the supply air blower motor. Adjust the resis-
tances in both the supply and the return air duct sys-
tems to balance the air distribution throughout the
conditioned space. The job specifications may require
that this balancing be done by someone other than the
equipment installer.
On VAV units be certain that the VFD drive is set
to maximum output, exhaust dampers are closed
and individual space damper boxes are full open.
VFD units with bypass must not be in bypass
mode ('LINE' position) unless all individual
space dampers are full open.
Johnson Controls Unitary Products
To check the supply air CFM after the initial balancing
has been completed:
1. Remove the two 5/16" dot plugs from the blower
motor and the filter access panels shown in Fig-
ures 13 and 14.
2. Insert at least 8" of 1/4 inch tubing into each of
these holes for sufficient penetration into the air
flow on both sides of the indoor coil.
The tubes must be inserted and held in a posi-
NOTE:
tion perpendicular to the air flow so that veloc-
ity pressure will not affect the static pressure
readings.
3. Using an inclined manometer, determine the pres-
sure drop across a dry evaporator coil. Since the
moisture on an evaporator coil may vary greatly,
measuring the pressure drop across a wet coil
under field conditions would be inaccurate. To
assure a dry coil, the compressors should be deac-
tivated while the test is being run.
PRESSURE DROP ACROSS A DRY COIL vs SUPPLY AIR CFM
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
4000
5000
6000
7000
NOMINAL AIR FLOW (SCFM)
FIGURE 21 - PRESSURE DROP ACROSS A DRY
INDOOR COIL VS SUPPLY AIR CFM
FOR ALL UNIT TONNAGES
4. Knowing the pressure drop across a dry coil, the
actual CFM through the unit can be determined
from the curve in Pressure Drop vs. Supply Air
CFM Figure 21.
Failure to properly adjust the total system air
quantity can result in extensive blower damage.
After readings have been obtained, remove the tubes
and reinstall the two 5/16" dot plugs that were removed
in Step 1.
DE-ENERGIZE
NOTE:
BEFORE TAKING ANY TEST MEASURE-
MENTS TO ASSURE A DRY INDOOR COIL.
284812-YIM-D-1008
8000
9000
10000
11000
12000
THE
COMPRESSORS
13000
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunline magnum wj180Sunline magnum wj300

Table of Contents