York SUNLINE MAGNADRY WR240 Technical Manual

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MAGNADRY WR240:
Table of Contents

Advertisement

Quick Links

TECHNICAL GUIDE
SUNLINE MagnaDRY™
GAS/ELECTRIC SINGLE
PACKAGE AIR CONDITIONERS
WR 180, 240 & 300
15 thru 25 NOMINAL TONS
11.9 EER (15 TONS), 11.0 EER (20 TONS),
10.0 EER (25 TONS)
®
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

DESCRIPTION

YORK Sunline MagnaDRY™ units are convertible single
package high efficiency rooftops. All models have independent
dual refrigerant circuits for efficient part load operation.
Although the units are primarily designed for curb mounting on
a roof, they can also be slab-mounted at ground level or set on
steel beams above a finished roof.
All units include:
• Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
• Two-stage cooling provided by dual independent
refrigeration circuits with expansion valves, filter-driers,
high and low pressure/loss of charge switches and
freezestats
• Scroll compressors
• Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
• Permanently lubricated motors
• Bottom or side air discharge configuration capability (field
convertible)
• Belt Drive Blower Motor with high static drive option
• Constant supply air volume (CV) with optional variable air
volume (VAV)
• Manufactured under the quality standards of ISO9001
• Simplicity® Control Board
• Zero-25% fixed air damper with hood
• Copper tube/aluminum fin coils
• Hinged filter access and toolless latched doors
• Rigging holes in base rails for lifting
• Single point power connection
• Complete factory package - tested, charged and wired
• CSA agency approvals on all units
WARRANTY
• One-year parts warranty
• A Five-year parts warranty on the compressors and
electric heat elements
• Ten-year parts warranty on the gas-fired heat exchangers
262292-YTG-B-0107

Advertisement

Table of Contents
loading

Summary of Contents for York SUNLINE MAGNADRY WR240

  • Page 1: Description

    FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE ® DESCRIPTION YORK Sunline MagnaDRY™ units are convertible single package high efficiency rooftops. All models have independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
  • Page 2: Table Of Contents

    DESCRIPTION ........1 PRODUCT NOMENCLATURE ..... . .3 FEATURES .
  • Page 3: Product Nomenclature

    262292-YTG-B-0107 PRODUCT NOMENCLATURE 15-25 Ton Sunline MagnaDRY™ Model Number Nomenclature W R 180 N24 A 2 A AA 1 0 1 2 4 A Product Category W = A/C, Single Pkg., R-22 w/6-Row Evap. Product Identifier R = 90.1 w/Reheat Nominal Cooling Capacity 180 = 15 Ton 240 = 20 Ton...
  • Page 4: Features

    FEATURES All models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging.
  • Page 5: Unit Cutaway

    • BAS Controls - York’s Magnum series units offer factory mounted BAS controls such as Novar, Honeywell, Johnson, and CPC.
  • Page 6: Reheat Control Board

    Anytime there is a call for 2 stages of cooling, the unit will not operate in the reheat mode, even if there is a call for dehumidification at "HUM". The unit will not operate in the reheat mode if there is any call for heating.
  • Page 7: Reheat Controls - Part 1

    262292-YTG-B-0107 FIGURE 3: REHEAT CONTROLS - PART 1 FIGURE 4: REHEAT CONTROLS - PART 2 Unitary Products Group UNIT CONTROL REHEAT CONTROL BOARD BOARD REHEAT SOLENOID UNIT CONTROL BOARD HUMIDIFY TERMINAL REHEAT RELAY RHTB REHEAT TERMINAL BLOCK REHEAT SOLENOID REHEAT SOLENOID REHEAT CONTROL...
  • Page 8: Factory-Installed Options

    • BAS - Building Automation System Controls (available on two-system cooling product only). Simplicity® INTELLI-Comfort™ CONTROL - The York® Simplicity® INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor.
  • Page 9: Field-Installed Accessories

    CO and humidity for ultimate comfort. Simplicity® INTELLI-Comfort™ with ModLINC CON- TROL - The York® Simplicity® INTELLI-Comfort™ with ModLINC control is factory installed. It includes all the fea- tures of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
  • Page 10 Power exhaust is not available as a field installed option. • ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
  • Page 11: Sound Power Rating

    262292-YTG-B-0107 TABLE 1: SOUND POWER RATING BLOWER UNIT SIZE WR180 6,000 1.00 1,080 WR240 8,000 1.00 1,120 WR300 10,000 1.30 1160 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only.
  • Page 12: Cooling Capacities For Wr180

    TABLE 4: COOLING CAPACITIES FOR WR180 Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 10.8 10.5 3750 10.2 11.0 10.6 4500 10.3 10.0 10.0 11.1 10.8 5250 10.4 10.1 10.1 11.2 10.9 6000 10.5 10.2 10.2 10.9 10.6 6750 10.3...
  • Page 13 262292-YTG-B-0107 TABLE 4: COOLING CAPACITIES FOR WR180 (CONTINUED) Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 15.8 15.6 3750 15.4 15.2 15.9 15.7 4500 15.5 15.2 15.2 15.9 15.7 5250 15.5 15.3 15.2 16.0 15.8 6000 15.6 15.4 15.3 15.8...
  • Page 14: Cooling Capacities For Wr240

    TABLE 5: COOLING CAPACITIES FOR WR240 Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 15.1 14.6 5000 14.2 13.8 15.2 14.8 6000 14.3 14.0 13.8 15.4 14.9 7000 14.4 14.1 13.9 15.5 15.1 8000 14.6 14.2 14.1 15.0 14.5 8500...
  • Page 15 262292-YTG-B-0107 TABLE 5: COOLING CAPACITIES FOR WR240 (CONTINUED) Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 21.3 21.0 5000 20.7 20.4 21.4 21.1 6000 20.8 20.5 19.7 21.6 21.3 7000 21.0 20.7 19.8 21.8 21.5 8000 21.1 20.8 20.0 21.4...
  • Page 16: Cooling Capacities For Wr300

    TABLE 6: COOLING CAPACITIES FOR WR300 Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 17.7 17.2 6250 16.7 16.3 20.7 20.1 7500 19.5 19.0 18.5 21.0 20.3 7750 19.7 19.2 18.7 21.2 20.6 8000 19.9 19.4 18.9 20.6 20.0 8650...
  • Page 17 262292-YTG-B-0107 TABLE 6: COOLING CAPACITIES FOR WR300 (CONTINUED) Air on Evaporator Coil Total Total Cap. Input (°F) (MBH) (kW) 26.6 26.0 6250 25.3 24.8 30.9 30.2 7500 29.4 28.8 28.4 31.1 30.4 7750 29.6 29.0 28.5 31.3 30.5 8000 29.8 29.2 28.7 30.5...
  • Page 18: Cooling Capacities For Wr180 (Alternate Reheat Mode)

    TABLE 7: COOLING CAPACITIES FOR WR180 (ALTERNATE REHEAT MODE) Air on Evaporator Coil Total Cap. (°F) (MBH) 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 4500 5250 6000 6750 7500 1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
  • Page 19: Cooling Capacities For Wr240 (Alternate Reheat Mode)

    262292-YTG-B-0107 TABLE 8: COOLING CAPACITIES FOR WR240 (ALTERNATE REHEAT MODE) Air on Evaporator Coil Total Cap. (°F) (MBH) 6000 7000 8000 8450 8900 6000 7000 8000 8450 8900 6000 7000 8000 8450 8900 1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
  • Page 20: Cooling Capacities For Wr300 (Alternate Reheat Mode)

    TABLE 9: COOLING CAPACITIES FOR WR300 (ALTERNATE REHEAT MODE) Air on Evaporator Coil Total Cap. (°F) (MBH) 7500 7750 8000 8500 9000 7500 7750 8000 8500 9000 7500 7750 8000 8500 9000 1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
  • Page 21: Wr180 Moisture Removal - Alt. Mode

    262292-YTG-B-0107 FIGURE 5: WR180 MOISTURE REMOVAL - ALTERNATE MODE FIGURE 6: WR180 MOISTURE REMOVAL - NORMAL MODE Unitary Products Group...
  • Page 22: Wr240 Moisture Removal - Alt. Mode

    Alternate mode @ various indoor (wet bulb/dry bulb) conditions 75/71 FIGURE 7: WR240 MOISTURE REMOVAL - ALTERNATE MODE Normal mode @ various indoor (wet bulb/dry bulb) conditions 75/71 FIGURE 8: WR240 MOISTURE REMOVAL - NORMAL MODE 20-Ton Moisture Removal @ 8000 cfm Outdoor Temp ºF 80/71 75/67...
  • Page 23: Wr300 Moisture Removal - Alt. Mode

    262292-YTG-B-0107 Alternate mode @ various indoor (wet bulb/dry bulb) conditions 75/71 FIGURE 9: WR300 MOISTURE REMOVAL - ALTERNATE MODE Normal mode @ various indoor (wet bulb/dry bulb) conditions 75/71 FIGURE 10:WR300 MOISTURE REMOVAL - NORMAL MODE Unitary Products Group 25-Ton Moisture Removal @ 8000 cfm Outdoor Temp ºF 80/71 75/67...
  • Page 24: Altitude Correction Factors

    CFM, STATIC PRESSURE, AND POWER - ALTITUDE AND TEMPERATURE CORRECTIONS The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level. The air flow rates listed in the standard blower performance tables are based on standard air at sea level.
  • Page 25: Factor

    262292-YTG-B-0107 FIGURE 11:ALTITUDE/TEMPERATURE CONVERSION FACTOR Unitary Products Group...
  • Page 26: Drive (Cooling Only) Downflow

    TABLE 11: WR180 BLOWER PERFORMANCE - 15 TON STANDARD DRIVE (COOLING ONLY) DOWNFLOW ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM 6284 956 3.50 4.20 6080 5918 957 3.25 3.89 5718 5590 958 3.05 3.66 5379 5226 959 2.79 3.34 4985 4801...
  • Page 27: Drive (Gas Heat) Downflow

    262292-YTG-B-0107 TABLE 12: WR180 BLOWER PERFORMANCE - 15 TON STANDARD DRIVE (GAS HEAT) DOWNFLOW ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM 6158 956 3.29 3.95 5958 5800 957 3.05 3.66 5604 5478 958 2.87 3.44 5271 5121 959 2.62 3.14 4885...
  • Page 28: Wr180 Blower Performance - 15 Ton High Static Drive (Cooling Only) Downflow

    TABLE 13: WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM 7695 1120 5.68 6.93 7434 1082 5.12 6.25 7139 1043 4.55 5.55 6853 1005 7344 1122 5.34 6.51 7089 1083 4.80 5.86 6791 1044 4.32 5.28 6497 1005 6994 1123 4.99 6.08 6751 1084 4.48 5.47 6477 1046 4.06 4.87 6190 1006 6711 1125 4.77 5.83 6478 1086 4.29 5.24 6196 1046 3.85 4.62 5864 1007...
  • Page 29: Wr180 Blower Performance - 15 Ton High Static Drive (Gas Heat) Downflow

    262292-YTG-B-0107 TABLE 14: WR180 BLOWER PERFORMANCE - 15 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM 7541 1120 5.34 6.51 7285 1082 4.81 5.87 6996 1043 4.28 5.22 6716 1005 7197 1122 5.02 6.12 6947 1083 4.51 5.50 6655 1044 4.06 4.88 6367 1005 6854 1123 4.69 5.72 6616 1084 4.21 5.14 6347 1046 3.81 4.58 6066 1006 6576 1125 4.49 5.48 6348 1086 4.04 4.84 6072 1046 3.62 4.35 5747 1007...
  • Page 30: Drive (Cooling Only) Downflow

    TABLE 15: WR240 BLOWER PERFORMANCE - 20 TON STANDARD DRIVE (COOLING ONLY) DOWNFLOW ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM 9557 1071 7.78 9.49 9313 1036 7.22 8.81 8842 1002 9720 1107 8.33 10.16 9159 1073 7.58 9.25 8901 1038 6.79 8.29 8426 1003 9345 1108 8.04 9.81 8775 1074 7.26 8.86 8503 1039 6.50 7.94 7980 1005 8975 1109 7.62 9.29 8390 1076 6.82 8.32 8089 1040 6.10 7.45 7576 1006 8590 1110 7.32 8.93 7977 1077 6.29 7.67 7643 1041 5.72 6.97 7123 1007...
  • Page 31: Drive (Gas Heat) Downflow

    262292-YTG-B-0107 TABLE 16: WR240 BLOWER PERFORMANCE - 20 TON STANDARD DRIVE (GAS HEAT) DOWNFLOW ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM 9892 1106 8.30 10.13 9366 1071 7.31 8.92 9127 1036 6.78 8.28 8665 1002 9526 1107 7.83 9.55 8976 1073 7.12 8.69 8723 1038 6.38 7.79 8257 1003 9158 1108 7.56 9.23 8600 1074 6.83 8.33 8333 1039 6.11 7.46 7820 1005 8796 1109 7.16 8.74 8222 1076 6.41 7.82 7927 1040 5.73 7.00 7424 1006...
  • Page 32: Wr240 Blower Performance - 20 Ton High Static Drive (Cooling Only) Downflow

    TABLE 17: WR240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW 11465 1201 11.98 14.62 10938 1167 10.57 12.90 10528 1131 9.67 11.80 9886 1096 8.54 10.43 9525 1063 7.55 9.21 9054 1027 7.05 8.60 11056 1202 11.46 13.98 10545 1168 10.23 12.48 10137 1133 9.20 11.23 9488 1097 8.17 9.98 9092 1064 7.32 8.93 8633 1028 6.45 7.87 10697 1203 10.97 13.39 10169 1169 9.78 11.93 10354 1204 10.68 13.03 9808 1170 9.42 11.50...
  • Page 33: Wr240 Blower Performance - 20 Ton High Static Drive (Gas Heat) Downflow

    262292-YTG-B-0107 TABLE 18: WR240 BLOWER PERFORMANCE - 20 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW 11236 1201 11.26 13.74 10719 1167 9.94 12.13 10317 1131 9.09 11.09 9688 1096 8.03 9.80 9335 1063 7.10 8.66 8873 1027 6.62 8.08 10835 1202 10.77 13.14 10334 1168 9.62 11.73 10483 1203 10.31 12.58 9966 1169 9.19 11.22 10147 1204 10.04 12.25...
  • Page 34: Drive (Cooling Only) Downflow

    TABLE 19: WR300 BLOWER PERFORMANCE - 25 TON STANDARD DRIVE (COOLING ONLY) DOWNFLOW 10636 1106 9.46 11.55 10163 1072 8.55 10.44 10312 1106 9.06 11.06 9824 1072 8.17 9975 1107 8.76 10.69 9466 1073 7.75 9629 1108 8.34 10.18 9108 1073 7.41 9262 1109 7.97 9.73 8730 1074 7.11...
  • Page 35: Drive (Gas Heat) Downflow

    262292-YTG-B-0107 TABLE 20: WR300 BLOWER PERFORMANCE - 25 TON STANDARD DRIVE (GAS HEAT) DOWNFLOW 10423 1106 8.89 10.85 9960 1072 8.04 10106 1106 8.52 10.40 9628 1072 7.68 9776 1107 8.24 10.05 9277 1073 7.28 9436 1108 7.84 9.57 8926 1073 6.97 9077 1109 7.49 9.14 8555 1074 6.68...
  • Page 36: Wr300 Blower Performance - 25 Ton High Static Drive (Cooling Only) Downflow

    TABLE 21: WR300 BLOWER PERFORMANCE - 25 TON HIGH STATIC DRIVE (COOLING ONLY) DOWNFLOW 11830 1216 12.80 15.62 11374 1181 11.51 14.05 11030 1146 10.55 12.87 10572 1111 9.50 11.59 10220 1075 8.67 10.58 9928 1041 7.91 9.65 11546 1217 12.31 15.02 11079 1181 11.12 13.57 10600 1147 10.00 12.20 10231 1112 9.11 11.12 9885 1076 8.28 10.10 9575 1040 7.52 9.18 11239 1217 11.87 14.49 10770 1182 10.79 13.17 10232 1147 9.63 11.75 9912 1112 8.87 10.82 9537 1077 7.94 9.69 9207 1042 7.08 8.63 10923 1218 11.48 14.01 10388 1183 10.25 12.51 10618 1219 11.14 13.60 10054 1185 9.82 11.98...
  • Page 37: Wr300 Blower Performance - 25 Ton High Static Drive (Gas Heat) Downflow

    262292-YTG-B-0107 TABLE 22: WR300 BLOWER PERFORMANCE - 25 TON HIGH STATIC DRIVE (GAS HEAT) DOWNFLOW 11593 1216 12.03 14.68 11147 1181 10.82 13.20 10809 1146 9.91 12.10 10361 1111 8.93 10.90 10016 1075 8.15 9.95 9729 1041 7.43 9.07 11315 1217 11.57 14.12 10857 1181 10.45 12.76 10388 1147 9.40 11.47 10026 1112 8.56 10.45 9687 1076 7.78 9.49 9384 1040 7.07 8.63 11014 1217 11.16 13.62 10555 1182 10.14 12.38 10027 1147 9.05 11.05 9714 1112 8.34 10.17 9346 1077 7.46 9.11 9023 1042 6.65 8.12 10705 1218 10.79 13.17 10180 1183 9.64 11.76 10406 1219 10.47 12.78...
  • Page 38: Blower Motor And Drive Data

    TABLE 23: BLOWER MOTOR AND DRIVE DATA MOTOR BLOWER MODEL DRIVE RANGE SIZE (RPM) HP FRAME Standard 790/970 184 T High 15 TON Speed 940/1130 7.5 213 T Access Speed 213 T 910/1100 Drive 20 TON Standard 215 T High Speed 1000/1180 15 254 T...
  • Page 39: Wr Electrical Data - Standard Drive Motor W/O Powered Conv. Outlet

    262292-YTG-B-0107 TABLE 26: WR ELECTRICAL DATA - STANDARD DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET COMPRESSORS MODEL VOLTAGE (TONNAGE) EACH EACH 22.4 22.4 (15) 10.9 30.1 30.1 (20) 15.5 12.1 42.3 42.3 (25) 17.6 14.5 NOTE 1: HACR Type per NEC. VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE...
  • Page 40: Wr Electrical Data - High Static Drive Motor W/O Powered Conv. Outlet

    TABLE 27: WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET COMPRESSORS MODEL VOLTAGE (TONNAGE) EACH EACH 22.4 22.4 (15) 10.9 30.1 30.1 (20) 15.5 12.1 42.3 42.3 (25) 17.6 14.5 NOTE 1: HACR Type per NEC. VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE...
  • Page 41: Wr Electrical Data - Low Airflow Drive Motor W/O Powered Conv. Outlet

    262292-YTG-B-0107 TABLE 28: WR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR W/O POWERED CONVENIENCE OUTLET COMPRESSORS MODEL VOLTAGE (TONNAGE) EACH EACH 30.1 30.1 (20) 15.5 12.1 42.3 42.3 (25) 17.6 14.5 NOTE 1: HACR Type per NEC. VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE 208/230-3-60 460-3-60...
  • Page 42: Wr Electrical Data - Standard Drive Motor With Powered Conv. Outlet

    TABLE 29: WR ELECTRICAL DATA - STANDARD DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET COMPRESSORS MODEL VOLTAGE (TONNAGE) EACH EACH 22.4 22.4 (15) 10.9 30.1 30.1 (20) 15.5 12.1 42.3 42.3 (25) 17.6 14.5 NOTE 1: HACR Type per NEC. VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE 208/230-3-60...
  • Page 43: Wr Electrical Data - High Static Drive Motor With Powered Conv. Outlet

    262292-YTG-B-0107 TABLE 30: WR ELECTRICAL DATA - HIGH STATIC DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET COMPRESSORS MODEL VOLTAGE (TONNAGE) EACH EACH 22.4 22.4 (15) 10.9 30.1 30.1 (20) 15.5 12.1 42.3 42.3 (25) 17.6 14.5 NOTE 1: HACR Type per NEC. VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE...
  • Page 44: Wr Electrical Data - Low Airflow Drive Motor With Powered Conv. Outlet

    TABLE 31: WR ELECTRICAL DATA - LOW AIRFLOW DRIVE MOTOR WITH POWERED CONVENIENCE OUTLET COMPRESSORS MODEL VOLTAGE (TONNAGE) EACH EACH 30.1 30.1 (20) 15.5 12.1 42.3 42.3 (25) 17.6 14.5 NOTE 1: HACR Type per NEC. VOLTAGE LIMITATIONS POWER SUPPLY VOLTAGE 208/230-3-60 460-3-60...
  • Page 45: Physical Data

    262292-YTG-B-0107 TABLE 32: PHYSICAL DATA MODELS CENTRIFUGAL BLOWER (Dia. x Wd.) EVAPORATOR BLOWER FAN MOTOR HP ROWS DEEP EVAPORATOR FINS PER INCH COIL FACE AREA (Sq. Ft.) PROPELLER DIA. (In.) CONDENSER FAN FAN MOTOR HP (FOUR PER UNIT) NOM. CFM TOTAL ROWS DEEP CONDENSER FINS PER INCH...
  • Page 46: Unit Dimensions Wr180, 240 & 300 (Front View)

    BLOWER MOTOR ACCESS (Location of Optional VFD Bypass) BLOWER COMPARTMENT ACCESS DOT PLUG 52-5/8 (For pressure drop reading) GAS OR ELECTRIC HEAT ACCESS VENT AIR OUTLET HOODS COMBUSTION AIR INLET HOOD UNIT BASE RAILS Shown separately to illustrate Bottom Duct openings. Power and Gas Piping Connection location.
  • Page 47: Rear View Dimensions

    262292-YTG-B-0107 Dimensions listed are for side duct flange openings; see Field Accessories for Side Duct Flange Kit. FIGURE 13:REAR VIEW DIMENSIONS NOTE:Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For bottom duct applications: Remove the side panels from the supply and return air compartments to gain access to the bottom supply and...
  • Page 48: Unit Dimensions Wr180, 240 & 300 (Rainhood)

    TABLE 35: MINIMUM CLEARANCES LOCATION Front Rear Left Side (Filter Access) Right Side (Cond. Coil) Below Unit Above Unit 1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material. 2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
  • Page 49: Unit Center Of Gravity

    262292-YTG-B-0107 FIGURE 15:UNIT CENTER OF GRAVITY FIGURE 16:TYPICAL UNIT APPLICATIONS Unitary Products Group 47.5" (15, 20, 25 TON) ROOF JACK INSTALLATION ROOF CURB INSTALLATION SLAB ON GROUND INSTALLATION...
  • Page 50: Four And Six Point Loads

    FIGURE 17:FOUR AND SIX POINT LOADS TABLE 36: FOUR AND SIX POINT LOADS Operating Unit Size Weight WR180 Gas 2900 WR240 Gas 3200 WR300 Gas 3300 WR180 Elec 2700 WR240 Elec 3000 WR300 Elec 3100 Operating Unit Size Weight WR180 Gas 2900 WR240 Gas 3200...
  • Page 51: Unit Roof Curb Dimensions

    262292-YTG-B-0107 FIGURE 18:UNIT ROOF CURB DIMENSIONS FIGURE 19:ROOF CURB DUCT OPENINGS DIMENSION The 2” space between the ducts allows for “jumping” an existing roof joist. The 58-1/2” overall dimension of the ducts allows ductwork penetration between roof joists that are spaced on 72” centers.
  • Page 52: Typical Field Wiring

    THERMOSTAT ( RCB ) TERMINALS REHEAT CONTROL BOARD TO REMOTE SENSOR 2ET04701324 IF USED Electronic programmable Thermostat 2ET0770010024 ( includes subbase). Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers when the thermostat switches to the set-back position. Dehumidistat closes on rise in humidity.
  • Page 53: Guide Specifications

    262292-YTG-B-0107 GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline Magnum™ units are convertible single package units. All models have dual independent refrigerant circuits for efficient part load operation and maximum comfort control.
  • Page 54 OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The 4 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.
  • Page 55 262292-YTG-B-0107 UNIT OPERATING CHARACTERISTICS Unit shall be capable of starting and running at 125° F outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 25° F outdoor temperature. Accessory low ambient kit shall be available for operation to 0°...
  • Page 56 Copyright © 2007 by Unitary Products Group. All rights reserved. Unitary Products Group • 4" THROW AWAY FILTERS • DISCONNECT SWITCH • SUPPLY AIR SMOKE DETECTOR • RETURN AIR SMOKE DETECTOR • LOW SPEED DRIVE (WR240 & WR300 only) 5005 York Drive 262292-YTG-B-0107 Supersedes: 262292-YTG-A-0706 Norman 73069...

This manual is also suitable for:

Sunline magnadry wr300Sunline magnadry wr180

Table of Contents