Air Balance; Rpm Selection; Indoor Blower Specifications; Power Exhaust Specifications - York ZF Series Installation Manual

R-410a 15 ton/53 kw 50 hertz
Hide thumbs Also See for ZF Series:
Table of Contents

Advertisement

Table 20: RPM Selection
Size
Model
HP
(Tons)
180
ZF
4.1
(15)
* Maximum blower speed is 1400 RPM for ZF180
Table 21: Indoor Blower Specifications
Size
Model
(Tons)
HP
180 (15)
ZF
4.1
Table 22: Power Exhaust Specifications
Voltage
HP
460-1-60
3/4
1. Motors are multi-tapped and factory wired for high speed.

Air Balance

Start the supply air blower motor. Adjust the resistances in both
the supply and the return air duct systems to balance the air
distribution throughout the conditioned space. The job
specifications may require that this balancing be done by
someone other than the equipment installer.
To check the supply air CFM after the initial balancing has been
completed:
1.
Remove the two 5/16" dot plugs from the blower motor and
the filter access panels shown in the Unit Dimensions and
Rear View Clearances Figure 7.
2.
Insert at least 8" of 1/4 inch tubing into each of these holes
for sufficient penetration into the air flow on both sides of
the indoor coil.
NOTE: The tubes must be inserted and held in a position
perpendicular to the air flow so that velocity pressure
will not affect the static pressure readings.
3.
Using an inclined manometer, determine the pressure drop
across a dry evaporator coil. Since the moisture on an
evaporator coil may vary greatly, measuring the pressure
drop across a wet coil under field conditions would be
inaccurate. To assure a dry coil, the compressors should
be deactivated while the test is being run.
Johnson Controls Unitary Products
Motor
Blower
Max BHP
Sheave
Sheave
4.72
1VP62
BK75
Motor
RPM
Eff.
SF
1450
0.89
1.15
Motor
1
RPM
QTY
LRA
1075
1
4.1
6 Turns
5 Turns
Open
Open
925
967
Motor Sheave
Datum Dia.
Frame
Bore (in.) Model
(in.)
184T
4.4 - 5.4
1 1/8
Motor
FLA
MCA
2.2
2.75
PRESSURE DROP ACROSS A DRY INDOOR COIL VS
0.7
0.65
0.6
0.55
0.5
0.45
0.4
0.35
0.3
0.25
4
5
Figure 23: Pressure Drop Across A Dry Indoor Coil Vs.
Supply Air CFM
4.
Knowing the pressure drop across a dry coil, the actual
CFM through the unit can be determined from the curve in
Pressure Drop vs. Supply Air CFM Figure 23.
Failure to properly adjust the total system air quantity
can result in extensive blower damage.
After readings have been obtained, remove the tubes and
reinstall the two 5/16" dot plugs that were removed in Step 1.
NOTE: De-energize the compressors before taking any test
measurements to assure a dry indoor coil.
Supply Air Drive Adjustment
The RPM of the supply air blower will depend on the required
CFM, the unit accessories or options and the static resistances
4 Turns
3 Turns
2 Turns
Open
Open
Open
1009
1051
1093
Blower Sheave
Datum Dia.
Bore (in.)
(in.)
1VP62
6.9
1
CFM @
0.1 ESP
5250
SUPPLY AIR CFM FOR ALL UNIT TONNAGES
180MBH
6
7
8
9
NOMINAL CFM (THOUSANDS) SUPPLY AIR
5326601-XIM-A-0117
1 Turn
Fully
Open
Closed
1135
N/A
Belt
Model
BK75
BX68
10
11
12
13
33