TABLE 13: WJ ELECTRICAL DATA W/POWERED CONVENIENCE OUTLET - HIGH STATIC DRIVE MOTOR
(CONT.)
COMPRESSORS
MODEL
(TON-
VOLTAGE
RLA
NAGE)
EACH
208
42.3
230
42.3
300
(25)
460
17.6
575
14.5
NOTE 1: HACR Type per NEC.
VOLTAGE LIMITATIONS
POWER SUPPLY
MIN.
208/230-3-60
187
460-3-60
414
575-3-60
518
1.
Utilization Range "A" in accordance with ARI Standard 110.
Johnson Controls Unitary Products
OD FAN
BLOWER
MOTORS
LRA
MOTOR
FLA EACH
EACH
FLA
245
2.4
38.6
245
2.4
38.6
125
0.9
19.3
100
0.6
16.2
1
VOLTAGE
NOMINAL VOLTAGE
MAX.
253
506
630
HEATER OPTION
ID
CONV
OUTLET
MODEL
KW
AMPS
None
E18
13.5
10.0
E36
27.0
E54
40.6
E72
54.1
None
E18
18.0
10.0
E36
36.0
E54
54.0
E72
72.0
None
E18
18.0
5.0
E36
36.0
E54
54.0
E72
72.0
None
E18
18.0
4.0
E36
36.0
E54
54.0
E72
72.0
ELECTRIC HEAT CORRECTION FACTORS
VOLTAGE
208
208
240
230
480
460
600
575
284812-YIM-D-1008
MIN.
CIRCUIT
AMPACITY
STAGES
AMPS
(AMPS)
~
~
~
153.4
1
37.5
153.4
2
74.9
154.4
2
112.7
201.6
2
150.2
210.9
~
~
~
153.4
1
43.3
153.4
2
86.6
169.0
2
129.9
190.7
2
173.2
234.0
~
~
~
67.9
1
21.7
67.9
2
43.3
84.5
2
65.0
95.3
2
86.6
117.0
~
~
~
55.7
1
17.3
55.7
2
34.6
68.6
2
52.0
77.2
2
69.3
94.5
kW CAP. MULTIPLIER
1.00
0.92
0.92
0.92
MAX.
FUSE/
1
BRKR
SIZE
(AMPS)
175
175
175
225
225
175
175
175
225
250
80
80
90
110
125
70
70
70
90
100
33