Wj240 Blower Performance - 20 Ton Standard Drive (Cooling Only) Downflow - York SUNLINE MAGNUM WJ240 Installation Manual

Gas/electric single package air conditioners
Hide thumbs Also See for SUNLINE MAGNUM WJ240:
Table of Contents

Advertisement

284812-YIM-D-1008
TABLE 20: WJ240 BLOWER PERFORMANCE - 20 TON STANDARD DRIVE (COOLING ONLY) DOWNFLOW
ESP CFM RPM KW BHP CFM RPM KW BHP CFM RPM KW BHP CFM RPM
0.4
9339 1014 7.07 8.63 8912 982 6.17 7.53 8487 949 5.55 6.77 8255 917
0.6
8855 1015 6.49 7.91 8480 983 5.99 7.31 8143 951 5.22 6.36 7781 918
0.8
8450 1016 6.11 7.45 8050 984 5.73 6.99 7704 952 5.13 6.26 7309 919
1.0
7994 1018 5.74 7.01 7590 985 5.08 6.19 7226 953 4.73 5.77 6793 920
1.2
7541 1019 5.33 6.50 7119 987 4.76 5.81 6744 954 4.11 4.93 6266 921
1.4
7086 1020 5.04 6.16 6653 988 4.27 5.21 6200 955 3.70 4.44 5743 922
1.6
6571 1022 4.83 5.89 6128 989 3.93 4.72 5650 956 3.30 3.96 5108 923
1.8
6055 1022 4.23 5.16 5606 990 3.59 4.31 5073 956 3.21 3.85 4511 923
2.0
5464 1023 3.73 4.47 4949 990 3.31 3.97
1 turn
10 HP motor
10000
1 turn
2 turns
9000
3 turns
4 turns
8000
5 turns
6 turns
7000
6000
5000
4000
3000
0.2
44
Blower Performance (Downflow Discharge)
-
-
2 turns
3 turns
7.5 HP motor
5 HP motor
20-Ton Standard Drive, Cooling Only, Bottom Connection
0.4
0.6
0.8
KW
BHP CFM RPM
5.07
6.18 7835 885
4.75
5.80 7357 887
4.34
5.30 6850 886
4.04
4.84 6330 888
3.72
4.46 5800 889
3.34
4.01 5189 890
3.15
3.79 4496 891
2.78
3.34 3788 892
-
-
-
-
-
-
4 turns
VP68 x BK110
1.0
1.2
External Static (" WC)
KW
BHP CFM RPM
4.63
5.65 7593 853
4.24
5.17 7081 854
4.11
4.93 6554 855
3.65
4.38 6009 856
3.39
4.07 5447 856
3.00
3.60 4762 858
2.64
3.16
-
2.03
2.43
-
-
-
-
-
-
5 turns
1.4
1.6
1.8
Johnson Controls Unitary Products
KW
BHP
4.39
5.36
3.83
4.59
3.63
4.36
3.26
3.91
2.86
3.43
2.59
3.11
-
-
-
-
-
-
-
-
-
6 turns
2.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunline magnum wj180Sunline magnum wj300

Table of Contents