An inadequately sized connecting cable which cannot
carry the required load can cause a voltage drop which
can burn out the appliance or tool and overheat the cable.
See Table 6.
„ When connecting a resistance load such as an
incandescent lamp or electric heater, a capacity of up
to the generating set's rated output (kW) can be used.
„ When connecting a fluorescent or mercury lamp, a
capacity of up to the generating set's rated output (kW)
multiplied by 0.6 can be used.
„ When connecting an electric drill or other power tools,
pay close attention to the required starting current
capacity.
When connecting ordinary power tools, a capacity of up
to the generating set's rated output (kW) multiplied by 0.8
can be used.
DANGER
Before connecting this generator to any building's
electrical system, a licensed electrician must install
an isolation (transfer) switch. Serious damage to
the building's electrical system may occur without this
transfer switch.
DCA10SPX4/DCA10SPXU4 • OPERATION MANUAL — REV. #2 (10/11/22) — PAGE 23
LOAD APPLICATION
MAXIMUM AMPS
Table 7 shows the maximum amps the generator can
provide. DO NOT exceed the maximum amps as listed.
Table 7. Generator Maximum Amps
Rated Voltage
Single Phase 120 Volts
Single Phase 240 Volts
Main Line Circuit Breaker Rating
Maximum Amps
20 amps (GFCI)
30 amps (L5-30R)
41.6 amps (continuous)
45 amps