CONNECTING LOADS
Loads can be connected to the generator via the output
receptacles (Figure 9). Make sure to read the operation
manual before attempting to connect a load to the generator.
To protect the output receptacles from overload, a 3-pole,
45-amp, main circuit breaker is provided. ALWAYS place
ALL circuit breakers in the OFF position prior to starting
the engine.
Figure 9. Connecting Loads
PAGE 22 — DCA10SPX4/DCA10SPXU4 • OPERATION MANUAL — REV. #2 (10/11/22)

LOAD APPLICATION

Single-Phase Load
Always be sure to check the nameplate on the generator
and equipment to ensure the wattage, amperage, frequency,
and voltage requirements are satisfactorily supplied by the
generator for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require
130–150% more wattage than the rating on the nameplate,
as the wattage is influenced by the efficiency, power factor,
and starting system of the equipment.
NOTICE
If wattage is not given on the equipment's nameplate,
approximate wattage may be determined by multiplying
the nameplate voltage by the nameplate amperage.
WATTS = VOLTAGE × AMPERAGE
The power factor of this generator is 1.0. See Table 5 below
when connecting loads.
Table 5. Power Factor By Load
Type of Load
Single-phase induction motors
Electric heaters, incandescent lamps
Fluorescent lamps, mercury lamps
Electronic devices, communication
equipment
Common power tools
Table 6. Cable Selection (60 Hz, Single-Phase Operation)
Load in Watts
Current
in
At 100
At 200
Amperes
Volts
Volts
2.5
300
600
5
600
1,200
7.5
900
1,800
10
1,200
2,400
15
1,800
3,600
20
2,400
4,800
CAUTION: Equipment damage can result from low voltage.
NOTICE
Motors and motor-driven equipment draw much greater
current for starting than during operation.
Power Factor
0.4–0.75
1.0
0.4–0.9
1.0
0.8
Maximum Allowable Cable Length
#10 Wire
#12 Wire
#14 Wire
1,000 ft.
600 ft.
375 ft.
500 ft.
300 ft.
200 ft.
350 ft.
200 ft.
125 ft.
250 ft.
150 ft.
100 ft.
150 ft.
100 ft.
65 ft.
125 ft.
75 ft.
50 ft.
#16 Wire
250 ft.
125 ft.
100 ft.