Dry Contact Relay Outputs; Dry Contact Pin Diagram; Dry Contact Wiring Diagram; Battery Temperature Sensor - Tripp Lite APSWX Series Owner's Manual

230v sine wave solar inverter chargers with integrated mppt solar charge controller
Hide thumbs Also See for APSWX Series:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
5. Communications

5.4 Dry Contact Relay Outputs

These normally-open dry output contacts will close when the following events occur: UPS Fault, Overload, AC Fault
and Battery Low Voltage. See the below table for contact port wiring specifications.

5.4.1 Dry Contact Pin Diagram

Description
COMM
UPS FAULT
OVERLOAD
AC FAULT
BATTERY LOW VOLTAGE

5.4.2 Dry Contact Wiring Diagram

Gauge (AWG)
Cable Size (mm
22
Relay Specifications:
• 15A @ 125V AC
• 10A @ 277V AC
• 7A @ 30V DC
5.5 Battery Temperature Sensor (Sealed Lead Acid Battery
Systems Only)
When the battery temperature sensor cable (sold separately) is connected between the BTS port on the APS and
a sealed lead-acid battery system, the APS will regulate the charge current when the battery temperature system is
too high.
1
2
Power
AC or DC Option
)
Torque Rating (max)
2
0.5
Pin
1
2
3
4
5
3
4
5
1.0 N•m
M3 word screwdriver
20
Description
COMM
UPS FAULT
OVERLOAD
AC FAULT
BATTERY LOW VOLTAGE
6
7
8
Tool
Cable Length (max)
9
10
10 m

Advertisement

Table of Contents
loading

This manual is also suitable for:

Apswx2k24vmpptApswx3k24vmpptAg-057bAg-057c

Table of Contents