EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1B – 2020.12
Wires: (3+GND)×1.5 mm²
1
2
3
3 (Optional) Drain tube heater cable:
▪ Make sure the heating element of the drain tube heater is completely inside
the drain tube.
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block and the earth screw.
▪ Fix the cable with cable ties.
Wires: (2+GND)×0.75 mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115 W (0.5 A)
8
Electrical installation
|
1 2 3