Daikin EPRA18DAV3 Installer's Reference Manual page 92

Hide thumbs Also See for EPRA18DAV3:
Table of Contents

Advertisement

8
|
Electrical installation
In case of V3 models
Installer reference guide
92
a1+a2 Power supply cable (field supply)
b1+b2 Interconnection cable (field supply)
c1+c2 (optional) Drain tube heater cable (field supply)
d Cable sleeves (factory-mounted)
4 Inside the switch box, connect the wires to the appropriate terminals, and fix
the cables with cable ties. See:
"In case of V3
models" [
"In case of W1
models" [
1 Power supply cable:
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block.
▪ Fix the cable with a cable tie.
Wires: 1N+GND
Maximum running current: Refer to name plate on unit.
b
L
a
N
b
L
1N~,
50 Hz,
N
230 V AC
a Power supply cable (field supply)
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse: 2 pole, 32 A fuse, C curve.
Q1DI Earth leakage circuit breaker (30 mA)(field supply)
2 Interconnection cable (indoor↔outdoor):
▪ Route the cable through the frame.
▪ Connect the wires to the terminal block (make sure the numbers match with
the numbers on the indoor unit) and the earth screw.
▪ Fix the cable with a cable tie.
4
 92]
4
 94]
L N PE
F1B
Q1DI
BRN
2
1
BLU
4
3
YLW/GRN
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
a
Daikin Altherma 3 H HT F
4P587502-1B – 2020.12