9
|
Configuration
Installer reference guide
156
You can...
Set the space operation mode permanently.
Restrict automatic changeover according to a monthly
schedule.
To check which space operation mode is currently used
The space operation mode is displayed on the home screen:
▪
When the unit is in heating mode, the
▪
When the unit is in cooling mode, the
The status indicator shows if the unit is currently in operation:
▪
When the unit is not in operation, the status indicator will show a blue pulsation
with an interval of approximately 5 seconds.
▪
While the unit is in operation, the status indicator will light up blue constantly.
To set the space operation mode
1 Go to [4.1]: Space heating/cooling > Operation mode
2 Select one of the following options:
▪
Heating: Only heating mode
▪
Cooling: Only cooling mode
▪
Automatic: The operation mode changes automatically
between heating and cooling based on the outdoor
temperature. Restricted per month according to the
Operation mode schedule [4.2].
Automatic heating/cooling changeover is only applicable for:
▪
Reversible models
▪
Heating only models + conversion kit (EKHVCONV2)
When Automatic is selected, the unit switches its operation mode, based on the
Operation mode schedule [4.2]. In this schedule, the end user indicates which
operation is allowed for each month.
To restrict automatic changeover according to a schedule
Conditions: You set the space operation mode to Automatic.
1 Go to [4.2]: Space heating/cooling > Operation mode
schedule.
2 Select a month.
3 For each month, select an option:
▪
Reversible: Not restricted
▪
Heating only: Restricted
▪
Cooling only: Restricted
4 Confirm the changes.
Location
Main menu
icon is shown.
icon is shown.
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1B – 2020.12