Parameter reference (LUI)
9.2 Setup (2.)
Low Temperature Value ON (2.8.6.2.)
Sets the temperature value (defined in ° C) at which the Low Temperature Alarm will activate.
Values
Low Temperature Value OFF (2.8.6.3.)
Sets the temperature value (defined in ° C) at which the Low Temperature Alarm will de-
activate.
Values
Assigned Relay (2.8.6.4.)
Determines which relay (if any) will be activated when the Low Temperature Alarm activates.
Options
Alarm State (2.8.6.5.)
Read only. Used to view the current state of the Low Temperature Alarm.
Options
9.2.8.7

High Temperature Alarm (2.8.7.)

Reported when process temperature is within a user-defined range (see High Temperature
Value ON (2.8.7.2.) (Page 207) or High Temperature Value OFF (2.8.7.3.) (Page 207)).
The temperature used for the alarm is the same temperature used for sound velocity
compensation (see Temperature Source (2.12.1.3.) (Page 222)).
Enable (2.8.7.1.)
Enables/disables High Temperature Alarm.
Options
206
Range: -273.0 to +273.0 °C (-459.0 to +523.0 °F)
Default: 0.0 °C
Range: -273.0 to +273.0 °C (-459.0 to +523.0 °F)
Default: 0.0 °C
*
ACTIVE
INACTIVE
*
Operating Instructions, 04/2021, A5E33329501-AG
NO RELAY
RELAY 1
RELAY 2
RELAY 3
ENABLED
DISABLED