High Calibration Point
Distance from Sensor Reference Point to High Calibration Point: usually process full level.
Value
Low Calibration Point
Distance from Sensor Reference Point to Low Calibration Point: usually process empty level.
Value
Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Note
• Response Rate can only be set through the Quick Start Wizard, and any changes made to
Fill Rate per Minute (2.3.1.) (Page 178), Empty Rate per Minute (2.3.2.) (Page 178), or
Damping Filter (2.3.3.) (Page 178) parameters following the completion of the wizard will
supersede the Response Rate setting.
• Response Rate always displays in m/minute.
Options
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy, faster settings allow for more rapid level
fluctuations.
Calculation Factors
Note
• The following five parameters will display in the wizard based on the PMD selected above.
• These parameters are used in the flow calculation formula (see Method of Flow
Calculation (Page 306)).
Flow Exponent
(PMD = EXPONENTIAL DEVICES)
The exponent for the flow calculation formula. (See Method of Flow Calculation (Page 306))
Value
SITRANS LUT400
Operating Instructions, 04/2021, A5E33329501-AG
Range: 0.000 to 60.000
Default: 0.000
Range: 0.000 to 60.000
Default: 60.000
SLOW (0.1 m/min)
MEDIUM (1.0 m/min)
FAST (10 m/min)
Default: SLOW (0.1 m/min)
Range: -999.000 to 9999.000
Default: 1.550
Commissioning
6.3 Quick Start Wizards
71