High Level Alarm - Siemens HydroRanger 200 HMI Operating Instructions Manual

Sitrans ultrasonic controllers
Hide thumbs Also See for HydroRanger 200 HMI:
Table of Contents

Advertisement

Parameter reference
8.3 Index selector examples
8.3.4

High level alarm

1. Navigate to Basic Setup (2.8.1.) (Page 193).
2. Set Relay Selector (2.8.1.1.) (Page 193) to Relay 1 to program the high level alarm.
3. Set Level Source (2.8.1.2) (Page 194) to Transducer 1.
4. Set Relay Function (2.8.1.4.) (Page 195) to Level.
5. Set ON Setpoint (2.8.1.5.) (Page 197) to 2 meters.
6. Set OFF Setpoint (2.8.1.6.) (Page 197) to 1.75 meters.
7. Repeat this procedure for each required relay. Ensure that the correct relay index is
selected in Relay Selector (2.8.1.1.) (Page 193).
160
HydroRanger 200 HMI
Operating Instructions, 06/2018, A5E36281317-AC