Maintenance Requirements - York MILLENNIUM YCAS 250 Manual

Air cooled liquid chiller
Table of Contents

Advertisement

MAINTENANCE REQUIREMENTS FOR YORK YCAS SCREW CHILLERS
PROCEDURE
Check oil level in oil separator sight glass
Check liquid line sight glass / moisture indicator
Record system operating pressures and temperatures
Check programmable operating setpoints and safety cut-outs
and assure they are correct for particular application.
Check condenser coils for dirt/debris and clean if necessary
Check compressor superheat on evaporator and economizer
TXV's; Check condenser and economizer subcooling
Check compressor and cooler heaters for operation
Sample compressor oil and replace oil if necessary
Leak check the chiller
1
Disconnect power source and lock out; Check tightness of
power wiring connections
1
* Reserved for customer use for any special site determined requirements.
1
This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK
equipment. A record of this procedure being successfully carried out must be maintained on file by the equipment owner should proof of adequate maintenance be
required at a later date for warranty validation purposes.
WEEKLY
QUARTERLY
X
X
X
X
1
1
SEMI-ANNUALLY
X
X
X
X
EVERY
YEARLY
*
___ HOURS
X
X