Temperature And Flows - York MILLENNIUM YCAS 250 Manual

Air cooled liquid chiller
Table of Contents

Advertisement

Technical Data
MODEL
LEAVING WATER
NUMBER
TEMPERATURE (°F)
YCAS
MIN.
0250EC
40
0270EC
40
0300EC
40
0330EC
40
0360EC
40
0400EC
40
0440EC
40
MODEL
LEAVING WATER
NUMBER
TEMPERATURE (°C)
YCAS
MIN.
0250EC
4.4
0270EC
4.4
0300EC
4.4
0330EC
4.4
0360EC
4.4
0400EC
4.4
0440EC
4.4
NOTES:
1. For leaving brine temperature below 40°F (4.40°C), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C) contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
46

TEMPERATURE AND FLOWS

(ENGLISH UNITS)
1
MAX.
2
55
55
55
55
55
55
55
Excessive flow, above the max GPM,
will damage the evaporator.
TEMPERATURE AND FLOWS
(SL UNITS)
1
2
MAX.
12.8
12.8
12.8
12.8
12.8
12.8
12.8
COOLER FLOW
(GPM
3
)
MIN.
MAX.
225
800
225
800
255
800
255
800
300
1060
330
1060
330
1060
COOLER FLOW
(L/S)
3
MIN.
MAX.
14.0
50.0
14.0
50.0
16.0
50.0
16.0
50.0
19.0
67.0
21.0
67.0
21.0
67.0
AIR ON
CONDENSER (°F)
MIN.
MAX
0
125
0
125
0
125
0
125
0
125
0
125
0
125
AIR ON
CONDENSER (°C)
MIN.
MAX
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7
-17.7
51.7