CONTROL POWER SUPPLY
CONTROL
MIN
MAX DUAL
NON-FUSED
UNIT
POWER
CIRCUIT
ELEMENT
VOLTAGE
SUPPLY
AMP.
FUSE SIZE
SWITCH SIZE
ALL MODELS
115-1-50/60
20A
20A 250V
30A 240V
W/O TRANS.
MODELS
-17
200-1-60
15A
15A 250V
30A 240V
WITH
-28
230-1-60
15A
15A 250V
30A 240V
TRANS.
-46
400-1-60
8A
8A 600V
30A 480V
*
-58
575-1-60
8A
8A 600V
30A 600V
* All primary and secondary wiring between transformer and control panel included.
YORK INTERNATIONAL
FORM 201.18-NM3
DISC.
85
YORK INTERNATIONAL
ELEMENTARY DIAGRAM
CAUTION:
No Controls (relays, etc.) should
be mounted in the Smart Panel
enclosure or connected to power
supplies in the control panel.
Additionally, control wiring not
connected to the Smart Panel
should not be run through the
cabinet. This could result in nui-
sance faults.
CAUTION:
Any inductive devices (relays)
wired in series with the flow
switch for start/stop, into the
Alarm circuitry, or pilot relays for
pump starters wired through mo-
tor contactor auxiliary contacts
must be suppressed with YORK
P/N 031-00808-000 suppressor
across the relay/contactor coil.
Any contacts connected to flow
switch inputs or BAS inputs on
terminals 13 - 19 or TB3, or any
other terminals, must be sup-
pressed with a YORK P/N 031-
00808-000 suppressor across
the relay/contactor coil.
CAUTION:
Control wiring connected to the
control panel should never be run
in the same conduit with power
wiring.
LD04266
FORM 201.18NM3
7
85A