Ycas 360 (English) - York MILLENNIUM YCAS 250 Manual

Air cooled liquid chiller
Table of Contents

Advertisement

Technical Data
CONTROL ENTRY
(12) 1/2"
CONDUIT K.O.'S
9"
POWER OPENING
(7" WIDE x
21" HIGH)
It is recommended that
power wiring enters
on the right side.
If left side entry is used,
be sure that space is
available for power wire
bending radius.
NOTES:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance,
reliable operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpre-
dictable air flow patterns and possible diminished performance. YORK's unit controls will optimize operation without nuisance high
pressure safety cutout; however, the system designer must consider potential performance degradation. Access to the unit control center
assumes the unit is no higher than on spring isolators. Recommended minimum clearances: Side to wall - 6'; rear to wall - 6'; control
panel end to wall - 4'; top - no obstructions allowed; distance between adjacent units - 10'. No more than one adjacent wall may be higher
than the unit.
FIG. 51 – MODEL 360 DIMENSIONS (ENGLISH DIMENSIONS)
104
DIMENSIONS - YCAS 360 (ENGLISH)
28"
2"
4 3/4"
2" TYP.
VIEW B-B
CONTROL
TRANSFORMER
SERVICE SWITCH
VIEW A-A
CONTROL
OPENING
(9" HIGH)
12"
POWER
OPENING
(21" HIGH)
B
B
C
21-3/8"
C
25-5/8" (EDGE OF
UNIT TO COOLER
CONNECTION)
91-13/16"
7"
2"
31 1/2"
VIEW C-C
7 1/2"
MICRO-COMPUTER
CONTROL CENTER
OPTIONS PANEL
LD05015
YORK INTERNATIONAL
42"
LD03996