Description of FINS Commands
Response code
Response code
0000 Hex
Normal completion
1001 Hex
Command length over
• The command length exceeds 2002 bytes.
1002 Hex
Insufficient command length
• The command length is less than four bytes.
1003 Hex
Number of elements/number of data mismatch
• The number of read start addresses does not match the
number of ITEMs.
1101 Hex
No type
• An unusable block address was specified in the parameter
type.
• The block address specified in the parameter type is an
unregistered function block.
• Function blocks other than System Common blocks cannot
be accessed as the RAM has not yet been initialized
(cleared) after a battery failure causes content of RAM to be
lost.
1103 Hex
Specified address out-of-range error
• There is not even one ITEM specified by the start address.
110B Hex
Response exceeds maximum response length
• The length of the read data section exceeds 968 bytes.
110C Hex
Other item parameter error
• Number of ITEMs is 0.
Section 6-3
Meaning