Basic Procedure for Using the Loop Controller
3. Setting up the Loop Controller and Other I/O Units
1,2,3...
Note
4. Downloading the function block data to the Loop Controller
1,2,3...
68
5. Using SCADA Software
Set the CSV tags and create the CSV tag files.
Refer to the CX-Process Tool Operation Manual.
1. Mount the Loop Controller and wire the Analog Input and Output Units.
The Loop Controller itself need not be wired.
See 2-2 Installation and refer to the manual for other Analog Input and Out-
put Units.
2. Set the unit number setting switch on the front panel of the Units.
3. Connect the Programming Devices.
Refer to Programming Devices (CX-Programmer or Programming Con-
sole) Operation Manual.
For CS1D CPU Units when the CS1D-LCB05D is being used, connect to the
active CPU Unit.
4. Turn power ON to the PLC.
5. Create I/O tables using the Programming Devices.
Refer to the Programming Devices (CX-Programmer or Programming
Console) Operation Manual.
6. If necessary, set the communications conditions of the serial communica-
tions port in the PLC Setup using the Programming Devices.
Refer to the Programming Devices (CX-Programmer or Programming
Console) Operation Manual.
7. Set the allocated Data Memory (D) on the Analog Input and Output Units
using the Programming Devices.
Refer to the Analog Input and Output Unit manuals.
1. Turn power OFF to the PLC.
2. Set the unit number setting switch on the front panel of the CPU Unit.
Refer to the CS1 PLC Operation Manual.
3. Connect the CPU Unit to the computer on which CX-Process Tool is run-
ning.
4. Turn the PLC ON.
5. Set the network address (000) and node address (01).
Refer to the CX-Process Tool Operation Manual.
6. Perform the Host Link connection operation on CX-Process Tool (File - Ini-
tialize Serial Port).
Refer to the CX-Process Tool Operation Manual.
7. Download the function block data to the Loop Controller specified in the
Function Block Data Sheet of CX-Process Tool (Execute - Download).
Refer to the CX-Process Tool Operation Manual.
Section 1-5