Errors and Alarm Troubleshooting
Code
Description
70
Illegal combina-
tion of function
blocks
Explanation
The function block on the pri-
mary loop side is not basic
PID or advanced PID when
bumpless processing
between primary/secondary
loops was specified in basic
PID or advanced PID.
The block address specified
as the master is not set to
Segment Program 2 (Block
Model 157) even though syn-
chronous operation is set for
Segment Program 2 (Block
Model 157).
The Segment Program 2
block specified as the master
was deleted during execu-
tion of Segment Program 2
(Block Model 157).
The block address of the
same Segment Program 2
(Block Model 157) block is
set in the "synchronous oper-
ation reference parameter
designation" (i.e., the Seg-
ment Program 2 block is set
as its own master).
A Basic PID block (Block
Model 011) or Advanced PID
block (Block Model 012) is
not set as the "source desig-
nation of PID block's MV out-
put" for Split Converter (Block
Model 169).
With the Segment Program 3
block (Block Model 158), the
function block with the block
address set in the target PID
block's address (ITEM 041) is
not a Basic PID or Advanced
PID block or 000 (not speci-
fied).
With a Basic PID block (Block
Model 011) or Advanced PID
block (Block Model 012), the
remote SP source designa-
tion is not the Segment Pro-
gram 2 or Segment Program
3 program output value
(ITEM 008) when PV lag off-
set correction (ITEM 110) is
enabled.
Operation at error
Running of the function block
in question is stopped.
The slave's initial output
value is not changed and
operation does not start.
The slave's output value is
held.
The initial values are not
changed and operation does
not start.
The initial values are not
changed and operation does
not start.
The program does not start.
Program outputs do not oper-
ate at the default settings.
PID control is executed with
no PV lag offset correction.
Section 7-1
Remedy
Check the function block
model number on the primary
loop side.
Specify the block address for
Segment Program 2 in the
master.
Specify the master correctly.
Specify the correct block
address in the "synchronous
operation reference parame-
ter designation."
Specify a Basic PID block
(Block Model 011) or
Advanced PID block (Block
Model 012) for the "source
designation of PID block's
MV output."
Check the settings for the tar-
get PID block's address
(ITEM 041).
Either disable PV lag offset
correction (ITEM 110) for the
Basic PID block (Block Model
011) or Advanced PID block
(Block Model 012), or set the
remote SP source designa-
tion (ITEM 021) to the Seg-
ment Program 2 or Segment
Program 3 program output
value (ITEM 008).
233