Vent Requirements

The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent
gas appliance must use its own separate vent system.
In addition to the requirements listed here, follow the requirements provided with the vent.
When the vent passes through a wall a wall thimble is required. When the vent passes through a
ceiling a support box or firestop is required. When the vent passes through the roof, a roof flashing
and storm collar are required. Follow the instructions provided with the vent for installing these items.
NOTE: Wall thimbles may have different dimensions than what is required by this heater.
The vent must maintain the required clearance to combustible materials to prevent a fire. Do not fill
air spaces with insulation.
Installation instructions for Simpson Dura-Vent may be found at www.duravent.com
Altitude Considerations
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety
hazard. Consult your dealer or installer if you suspect an improperly adjusted air shutter.
This heater has been tested at altitudes ranging from sea level to 6,000 feet (1,800 M). In this testing
we have found that the heater, with its standard orifice, burns correctly with just an air shutter
adjustment.
Approved Vent – Top Vent Configuration
Use 6-5/8" (168mm) diameter Simpson Dura-Vent Direct-Vent Pro (or GS)*.
* Other vent may be approved with this stove. Check with the vent manufacturer for details.
Always use the high-wind cap (part # 46DVA-VCH or 46DVA-HC).
Approved Vent – Rear Vent Configuration
WITH NO VENT RISE: Must use Travis Industries Minimum Vent Kit D (Part # 96200317) only.
WITH VENT RISE: Use Travis Industries Rear Vent Conversion ( Part # 94400998) with 8" (204mm)
diameter Simpson Dura-Vent Direct-Vent Pro (or GS)*. Always use the high-wind cap (part #
58DVA-VCH or 58DVA-HC).
* Other vent may be approved with this stove. Check with the vent manufacturer for details.
Vent Installation
Slide the vent sections together and turn 1/4 turn until the sections lock in place.
Screws are not required to secure the vent. However, three screws may be used to
secure vent sections together if desired.
Horizontal sections require a 1/4" rise every 12" of travel
Horizontal sections require non-combustible support every three feet (e.g.: plumbing tape)
© Travis Industries
Installation
Minimum Clearance
Top Vent Configuration
Rear Vent Configuration
(for qualified installers only)
Above, Below or Side of Vent
1"
1"
2/23/18 - 1479
Greenfield GSR2-Aust