Stove Installation

Floor Protection Requirements

Stove must be placed on the Travis Industries legs or pedestal.
Floor protection must extend to the sides, rear, and front of the stove (see "Clearances" below for
minimum floor protection).
NOTE: When installed with reduced-clearance connector, the clearance to the backwall may be less
than the floor protection requirement. In this case the floor protection must extend to the wall.
Floor protection must be non-combustible and at least .018" thick (26 gauge).

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within (e.g., drapes, doors),
36" (914mm) of the front of the stove.
If the stove is placed in a location where the ceiling height is less than 7' (2,134mm), additional
requirements may apply (contact your local building official).
Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):

Clearances

The following clearances must be met (see Figure 2)
Clearance Requirements:
A*
Sidewall to stove
B*
Backwall to stove
C*
Cornerwall to stove
D
Front Hearth
E
Side Hearth
F
Back Hearth
* Clearances to combustible material are according to heater test results using a standard flue kit,
(AS/NZS 2918:2001) fitted with 1 length 900mm deco mesh with a heat shield or 1 length 900mm x
120° stainless steel heat shield as a minimum. Any further enquiries please contact Dragon
Wholesaling Pty Ltd on 1800 064 234.
© Travis Industries
(for qualified installers only)
No Flue Shield
N/A
N/A
150mm
300mm
200mm
152mm
100-01275
With Flue Shield
350mm
150mm
150mm
300mm
200mm
152mm
Figure 2
4111122