Floor Protection Requirements; Stove Placement Requirements; Clearances - Lopi Cape Cod Owner's Manual

Hide thumbs Also See for Cape Cod:
Table of Contents

Advertisement

8
Stove Installation

Floor Protection Requirements

Floor protection must extend to the sides, rear, and front of the stove (see "Clearances" below for
minimum floor protection).
Floor protection must be non-combustible and at least .018" (.45mm) thick (26 gauge).

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within 36" (914mm) of the
front of the stove (drapes, doors, etc.)
If the stove is placed in a location where the ceiling height is less than 7' (2.134M), it must follow the
requirements in the section "Alcove Installation Requirements"
Must maintain the clearances to combustibles listed below (drywall, furniture)
The stove requires an air source to operate. Combustion air starvation will result in poor performance
or smoke in the house.

Clearances

The following clearances must be met (see Figure 2 and Figure 3):
Minimum Clearance
A
Sidewall to stovetop
B
Back wall to stovetop
C
Corner wall to stovetop
D
Connector to sidewall
E
Connector to back wall
F
Connector to corner wall
G
Floor protection side and back
H
Floor protection front
*Reduced clearance installations require one of the chimneys and connectors listed below:
AMERI-TEC model DCC with model HS chimney
DURAVENT model DVL with DURATEC or DURA-PLUS chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
METALFAB model DW connector with TG chimney
OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney
SECURITY model DP connector with SECURITY model ASHT or S2100 chimney
SELKIRK METALBESTOS model DS connector with model SSII chimney
OLYMPIA VENTIS with Ventis double wall black stove pipe
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.
NOTE: Standard residential installations with reduced clearance connector may use the clearance
determined by the manufacturer of the connector for the connector to wall clearance or the clearance
listed in this manual. Offsets must be used to maintain the stove to wall clearance.
© Travis Industries
(for qualified installers only)
Single wall
Connector
12 ¾" (324mm)
14 ¾" (375mm)
7 ¼" (185mm)
26" (661mm)
15" (381mm)
17 ½" (445mm)
6" US / 8" Canada
(153mm / 204mm)
16" US / 18" Canada
(407mm / 458mm)
100-01282_000
Reduced
Clearance*
12 ¾" (324mm)
11 ¾" (299mm)
7 ¼" (185mm)
26" (661mm)
12" (305mm)
17" (432mm)
6" US / 8" Canada
(153mm / 204mm)
16" US 18" Canada
(407mm / 458mm)
4111128