8
Stove Installation
SAFETY NOTICE:
Please read this entire manual before you install and use your new room heater. Failure to
follow instructions may result in property damage, bodily injury, or even death. Contact local
building or fire officials about restrictions and installation inspection requirements in your area.
Packing List
Wood moisture meter
Bypass tool
Planning the Installation
We suggest that you have an authorized Travis Industries dealer install your stove. If you install the
stove yourself, your authorized dealer should review your installation plans.
Check with local building officials for any permits required for installation of this stove and notify your
insurance company before proceeding with installation.
The location of your wood heater in your home will decide how affectively the heat produced will spread
throughout your house. Attention to the home design with consideration of natural convection and air
circulation should be taken into account when choosing the placement of your heater within the home.
Preparation for Installation
Check for damage to the exterior of the stove (dents should be reported, scratches can be fixed by
applying touch up paint).
Check the interior of the firebox (replace cracked firebrick and make sure baffle is in place).
The stove can be lightened by removing the firebricks and baffle (page 30) - replace before operation.
Floor Protection Requirements
Stove must be placed on the Travis Industries legs.
Floor protection must extend to the sides, rear, and front of the stove (see "Clearances" below for
minimum floor protection).
Floor protection must be min 12mm (compressed board). The Thermal resistivity of the floor
protector is 0.08m².K/W for 6mm thick sheets.
Stove Placement Requirements
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36"
(914mm) of the front of the stove
If the stove is placed in a location where the ceiling height is less than 7' (2134mm), it must follow the
requirements in the section "Alcove Installation Requirements"
Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):
© Travis Industries
(for qualified installers only)
6/12/2019 - 1517
Endeavor (AUST)