Electric Heat; Hkr Installation; Location - Goodman ARUF Series Installation & Operating Instructions Manual

Hide thumbs Also See for ARUF Series:
Table of Contents

Advertisement

If an incorrect unit is supplied, it must not be installed and
it is to be returned to the supplier. The manufacturer
assumes no responsibility for the installation of incorrectly
delivered units.
The evaporator coil contains a high-pressure inert gas
holding charge.

ELECTRIC HEAT

WARNING
REFER TO THE "INSTALLING ELECTRIC HEAT" SECTION
OF THIS MANUAL AND THE INSTRUCTIONS PROVIDED
WITH THE HEAT KIT FOR THE CORRECT INSTALLATION
PROCEDURE.
WARNING
THE ELECTRICAL CHARACTERISTICS OF THE AIR
HANDLER, THE ELECTRIC HEAT KIT, AND THE SUPPLY
POWER MUST AGREE, UNLESS USING HKR3 (3 PHASE)
SERIES HEAT KIT. THIS AIR HANDLER DOES NOT HAVE
FACTORY INSTALLED ELECTRIC HEAT. ELECTRIC HEAT
IS AVAILABLE AS AN ACCESSORY. IF INSTALLING THIS
OPTION, THE ONLY HEAT KITS THAT CAN BE USED ARE
THE HKR SERIES AS INDICATED BELOW: NOTE: THE
AMANA® BRAND EHK, ECB, EDB, AND EDK KITS ARE
NOT APPROVED FOR USE WITH THESE AIR HANDLERS.
The heating mode temperature rise is dependent upon the
system airflow, the supply voltage, and the heat kit size
(kW) selected. Use Tables 1-3 to determine the
temperature rise (
o
F).
HEAT KIT NOMINAL kW
CFM
3
5
6
600
18
28
35
800
13
21
26
1000
11
17
21
1200
9
14
18
1400
8
12
15
1600
7
10
13
1800
6
9
12
2000
5
8
11
230/1/60 Supply Voltage - Temperature Rise Table °F
HEAT KIT NOMINAL kW
CFM
3
5
6
600
17
27
34
800
13
20
25
1000
10
16
20
1200
8
13
17
1400
7
11
14
1600
6
10
13
1800
6
9
11
2000
5
8
10
220/1/60 Supply Voltage - Temperature Rise Table °F
8
10
15
20
41
31
42
25
34
50
21
28
42
56
18
24
36
48
15
21
31
42
14
19
28
37
12
17
25
34
Table 1
8
10
15
20
39
30
40
24
32
48
20
27
40
53
17
23
34
46
15
20
30
40
13
18
27
36
12
16
24
32
Table 2
CFM
3
600
16
25
800
12
19
1000
10
15
1200
8
13
1400
7
11
1600
6
1800
5
2000
5
208/1/60 Supply Voltage - Temperature Rise Table °F
Note: For installations not indicated above the following
formula is to be used:
TR = (kW x 3412) x (Voltage Correction) x 1.08 / CFM
Where: TR
KW
3412
Voltage Correction
1.08
CFM
NOTE: The Temperature Rise Tables can also be used to
determine the air handler airflow delivery. When using these
tables for this purpose set the room thermostat to maximum
heat and allow the system to reach steady state conditions.
Insert two thermometers, one in the return air and one in
the supply air. The temperature rise is the supply air
temperature minus the room air temperature.
21
Use HKR specification sheets to determine the HKR
available for a given air handler.

HKR INSTALLATION

62
Follow instructions listed in Installation and Operating
53
Instructions shipped with the heat kit.
46

LOCATION

41
37
WARNING
AIR HANDLERS ARE DESIGNED FOR INDOOR
INSTALLATION ONLY. DO NOT INSTALL OUTDOORS.
Consideration to minimize the length of refrigerant tubing
must be given when installing Air Handlers. Do not install
21
the air handler in a location either above or below the
condenser that violates the instructions provided with the
condenser. The clearance from a combustible surface to
the unit is 0". However, service clearance is to take
59
precedence. Allow a minimum of 24" in front of the unit for
51
service clearance. When installing in an area directly over
44
a finished ceiling (such as an attic), an emergency drain
39
pan is required directly under the unit. See local and state
35
codes for additional requirements. When installing this unit
in an area that may become wet, elevate the unit with a
5
HEAT KIT NOMINAL kW
5
6
8
10
32
37
24
38
38
19
22
30
16
19
25
14
16
22
9
12
14
19
8
11
12
17
8
10
11
15
Table 3
= Temperature Rise
= Heater Kit Actual kW
= Btu per kW
=.96 (230 Supply Volts)
=.92 (220 Supply Volts)
=.87 (208 Supply Volts)
= Constant
= Measured Airflow
15
20
21
46
38
51
56
33
43
48
28
38
42
25
34
37
23
30
34

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arpf seriesAdpf seriesAepf series

Table of Contents