Aepf Motor Orientation; Conversion To Downflow - Goodman ARUF Series Installation & Operating Instructions Manual

Hide thumbs Also See for ARUF Series:
Table of Contents

Advertisement

1. Loosen the 13/16 nut 1 TURN ONLY. No pressure loss
indicates possible leak.
2. Remove the nut and discard the cap.
3. Remove the check piston to verify it is correct. See
piston kit chart in instructions.
4. Use a tube cutter to remove the spin closure on the
suction line.
5. Remove the tailpiece clamped to the exterior.
6. Slide the 13/16 nut into position. Braze tailpiece to
the liquid tube.
7. Insert the suction line into the connection, slide the
insulation and the rubber grommet at least 18" away
from the braze joint.
8. AFTER THE TAILPIECE HAS COOLED, position the
seal and hand tighten the nut.
9. Torque the 13/16 nut to 20-30 ft-lbs. [2.77-4.15 meter
kg].
10. Replace suction line grommet and insulation.
CAP
13/16" NUT
TAILPIECE
SEAL
SUCTION LINE
WITH SPIN CLOSURE

AEPF MOTOR ORIENTATION

If the unit is in the upflow position, there is no need to rotate
the motor. If the unit is in the downflow or horizontal position,
loosen motor mount and rotate motor as shown in Figure 3
Be sure motor is oriented with the female connections on
the casing down. If the motor is not oriented with the
connections down, water will collect in the motor and may
cause premature failure.
PISTON
Figure 1
RUBBER
GROMMET
Figure 2
FRONT VIEW
FOR OPTIONAL
SAFETY GND USE
MOUNTING BOLTS
AEPF Motor Orientation

CONVERSION TO DOWNFLOW

"D" nomenclature models are factory equipped for "Dedicated
Downflow" operation and no field conversion is required.
Conversion to downflow MUST be performed in an area that
allows access to all sides prior to placing the air handler in
its final location. To prevent the evaporator coil pan from
"sweating" the DPI accessory insulation kit is to be used
when performing this conversion. NOTE: The DPI kit is not
supplied with this product and is to be purchased separately.
See Table 8 for the correct DPI kit.
ARUFor ARPF
model
1729
1824
3030
1931
3642
3743
4860
Refer to Figures 4 through 6 for the location of the
components referenced in the following steps. Figure 4
illustrates the new installation location for the removed
components.
1. Before inverting the air handler, remove all access
panels, the coil rear channel bracket, and the filter close-
off panel.
2. Remove the evaporator coil and the horizontal drain pan.
Discard horizontal drain pan.
3. Install the provided plastic plug into the vacated access
panel.
4. Remove the two (2) zee coil support brackets and
insulation retaining brackets.
5. Remove the tie bracket.
6. Install the DPI Insulation Kit onto the bottom of the
drain pan.
8
SIDE VIEW
FEMALE CONNECTIONS
Figure 3
AEPF model
Insulation Kit
N/A
DPI18-30/20
1830
DPI36-42/20
3036
DPI48-61/-20
4260
Table 8