Pre-Installation Instructions; Location; Ductwork; Return Ductwork - Goodman ADPF Installation & Operating Instructions Manual

Goodman mfg. co. lp. air conditioner user manual
Hide thumbs Also See for ADPF:
Table of Contents

Advertisement

Pre-Installation Instructions

Carefully read all instructions for the installation prior to in-
stalling product. Make sure each step or procedure is under-
stood and any special considerations are taken into account
before starting installation.
and supplies needed to complete the installation. Some items
may need to be purchased locally. Make sure everything
needed to install the product is on hand before starting.

Location

NOTE: Air handlers are designed for indoor installation
only.
Give special consideration to minimizing the length of refrig-
erant tubing when installing air handlers. Refer to Remote
Cooling/Heat Pump Service Manual, TP-106 Long Line Set
Application R-22 or TP-107 Long Line Set Application R-410A
for guidelines. The unit clearance from a combustible sur-
face may be 0". However, service clearance is to take prece-
dence. In addition allow a minimum of 24" in front of the unit
for service clearance.
Do not install the air handler in a location that violates the
instructions provided with the condenser.
If the unit is located in an area with high ambient temperature
and/or high humidity the air handler maybe subject to nui-
sance sweating of the casing. On these installations a wrap
of 2" fiberglass insulation with a vapor barrier is recom-
mended.
Consult all appropriate regulatory codes prior to determining
final clearances. When installing this unit in an area that may
become wet, elevate the unit with a sturdy, non-porous ma-
terial. In installations that may lead to physical damage (i.e. a
garage) it is advised to install a protective barrier to prevent
such damage.

Ductwork

This air handler is designed for a complete supply and return
ductwork system.
Do not operate this product without all the ductwork
attached.
To ensure correct system performance, the ductwork is to be
sized to accommodate 375-425 CFM per ton of cooling with
the static pressure not to exceed .5" WC. Inadequate duct
work that restricts airflow can result in improper performance
and compressor or heater failure. Ductwork is to be con-
structed in a manner that limits restrictions and maintains
suitable air velocity. Ductwork is to be sealed to the unit in a
manner that will prevent leakage.

Return Ductwork

DO NOT TERMINATE THE RETURN DUCTWORK IN AN
AREA THAT CAN INTRODUCE TOXIC, OR OBJECTION-
ABLE FUMES/ODORS INTO THE DUCTWORK. The return
ductwork is to be introduced into the air handler bottom (upflow
configuration).

Return Air Filters

Each installation must include a return air filter. This filtering
may be performed at the air handler or externally such as a
Assemble all tools, hardware
return air filter grille. Air handlers mounted in the downflow
orientation, including "B" series, require external filtering. A
washable filter is available as an accessory. To ensure opti-
mum performance frequent filter cleaning is advised. Refer
to Table 1 for the appropriate filter.
ARUF
ATUF
ADPF ASPF
ARPF
1729
1824
1824
1824
3030
3030
3030
1931
1931
3636
3636
3642
3642
3042
3743
3743
4860
4860
4860

Electric Heat

Refer to this manual in combination with the instructions pro-
vided with the heat kit for the correct installation procedure.
The air handlers listed in this manual do not have factory
installed electric heat. Electric heat is available as an acces-
sory. If installing this option, the ONLY heat kits that can be
used are the HKR series.
NOTE: The Amana® brand EHK, ECB, EDB, and EDK kits
are NOT approved for use with these air handlers.
The heating mode temperature rise is dependent upon the
system airflow, the supply voltage, and the heat kit size (kW)
selected. Use Tables 2, 3, and 4 to determine the tempera-
º
ture rise (
F).
HEAT KIT NOMINAL kW
CFM
3
5
600
18
28
800
13
21
1000
11
17
1200
9
14
1400
8
12
1600
7
10
1800
6
9
2000
5
8
230/1/60 Supply Voltage - Temperature Rise Table °F
HEAT KIT NOMINAL kW
CFM
3
5
600
17
27
800
13
20
1000
10
16
1200
8
13
1400
7
11
1600
6
10
1800
6
9
2000
5
8
220/1/60 Supply Voltage - Temperature Rise Table °F
4
Filter
Number
Required
N/A
FIL 18-32
1830 FIL 36-42
3036
FIL 48-61
3137
4260
Table 1
6
8
10
15
35
41
26
31
42
21
25
34
50
18
21
28
42
15
18
24
36
13
15
21
31
12
14
19
28
11
12
17
25
Table 2
6
8
10
15
34
39
25
30
40
20
24
32
48
17
20
27
40
14
17
23
34
13
15
20
30
11
13
18
27
10
12
16
24
Table 3
Qty
1
1
1
20
21
56
62
48
53
42
46
37
41
34
37
20
21
53
59
46
51
40
44
36
39
32
35