Return Air Filters; Electric Heat - Goodman ARUF**14 Series Installation & Operating Instructions Manual

Hide thumbs Also See for ARUF**14 Series:
Table of Contents

Advertisement

TIONABLE FUMES/ODORS INTO THE DUCTWORK. The return ductwork is to be connected to the air handler
bottom (upflow configuration).

10 Return Air Filters

Each installation must include a return air filter. This filtering may be performed at the air handler using the factory filter rails
or externally such as a return air filter grille. When using the factory filter rails, a nominal 16x20x1", 20x20x1" or 24x20x1"
(actual dimension must be less than 23-½"x20") filter can be installed on a B, C and D cabinet respectively (the cabinet size
is the seventh letter of the model number).

11 Electric Heat

Refer to the installation manual provided with the electric heat kit for the correct installation procedure. All electric heat must
be field installed. If installing this option, the ONLY heat kits that are permitted to be used are the HKS series. Refer to the
air handler unit's Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible with a given
air handler. No other accessory heat kit besides the HKS series may be installed in these air handlers.
The heating mode temperature rise is dependent upon the system airflow, the supply voltage, and the heat kit size (kW)
selected. Use data provided in Tables 2, 3 and 4 to determine the temperature rise (°F).
NOTE: For installations not indicated above the following formula is to be used:
Where:
TR
= Temperature Rise
kW
= Heater Kit Actual kW
3412 = Btu per kW
VC*
= .96 (230 Supply Volts)
= .92 (220 Supply Volts)
= .87 (208 Supply Volts)
1.08 = Constant
CFM = Measured Airflow
*VC (Voltage Correction)
NOTE: The Temperature Rise Tables can also be used to estimate
the air handler airflow delivery. When using these tables for this
purpose set the room thermostat to maximum heat and allow the
system to reach steady state conditions. Insert two thermometers,
one in the return air and one in the supply air. The temperature rise
is the supply air temperature minus the room air temperature. Using
the temperature rise calculated, CFM can be estimated from the
TR formula above. See Technical Manual and/or Service Manual
for more information.
TR = (kW x 3412) x (Voltage Correction) / (1.08XCFM)
CFM
3
800
12
1000
9
1200
8
1400
7
1600
6
1800
5
2000
5
230/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
CFM
3
800
11
1000
9
1200
7
1400
6
1600
6
1800
5
2000
4
220/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
10
HEAT KIT NOMINAL kW
5
6
8
10
15
19
23
31
37
15
19
25
30
44
12
15
21
25
37
11
13
18
21
32
9
12
15
19
28
8
10
14
16
25
7
9
12
15
22
Table 2
HEAT KIT NOMINAL kW
5
6
8
10
15
18
22
30
35
14
18
24
28
42
12
15
20
24
35
10
13
17
20
30
9
11
15
18
27
8
10
13
16
24
7
9
12
14
21
Table 3
19/20 25
49
62
42
53
37
46
33
41
30
37
19/20 25
47
59
40
51
35
44
31
39
28
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents