Return Ductwork

DO NOT TERMINATE THE RETURN DUCTWORK IN AN
AREA THAT CAN INTRODUCE TOXIC, OR OBJECTION-
ABLE FUMES/ODORS INTO THE DUCTWORK. The return
ductwork is to be introduced into the air handler bottom (upflow
configuration).

Return Air Filters

Each installation must include a return air filter. This filtering
may be performed at the air handler or externally such as a
return air filter grille. Air handlers mounted in the downflow
orientation, including "B" series, require external filtering. A
washable filter is available as an accessory. To ensure opti-
mum performance frequent filter cleaning is advised. Refer
to Table 1 for the appropriate filter.
ASPF
Filter Number Qty Required
1830
3137
4260

Electric Heat

Refer to this manual in combination with the instructions pro-
vided with the heat kit for the correct installation procedure.
The air handlers listed in this manual do not have factory
installed electric heat. Electric heat is available as an acces-
sory. If installing this option, the ONLY heat kits that can be
used are the HKR series.
NOTE: The Amana® brand EHK, ECB, EDB, and EDK kits
are NOT approved for use with these air handlers.
The heating mode temperature rise is dependent upon the
system airflow, the supply voltage, and the heat kit size (kW)
selected. Use Tables 2, 3, and 4 to determine the tempera-
º
ture rise (
F).
HEAT KIT NOMINAL kW
CFM
3
5
6
600
18
28
35
800
13
21
26
1000
11
17
21
1200
9
14
18
1400
8
12
15
1600
7
10
13
1800
6
9
12
2000
5
8
11
230/1/60 Supply Voltage - Temperature Rise Table °F
FIL 36-42
1
FIL 48-61
1
Table 1
8
10
15
20
41
31
42
25
34
50
21
28
42
56
18
24
36
48
15
21
31
42
14
19
28
37
12
17
25
34
Table 2
CFM
3
600
17
800
13
1000
10
1200
8
1400
7
1600
6
1800
6
2000
5
220/1/60 Supply Voltage - Temperature Rise Table °F
CFM
3
600
16
800
12
1000
10
1200
8
1400
7
1600
6
1800
5
2000
5
208/1/60 Supply Voltage - Temperature Rise Table °F
NOTE: For installations not indicated above the following
formula is to be used:
TR = (kW x 3412) x (Voltage Correction) x 1.08 / CFM
Where: TR
kW
3412
Voltage Correction
1.08
CFM
NOTE: The Temperature Rise Tables can also be used to
determine the air handler airflow delivery. When using these
21
tables for this purpose set the room thermostat to maximum
heat and allow the system to reach steady state conditions.
Insert two thermometers, one in the return air and one in the
supply air. The temperature rise is the supply air temperature
62
minus the room air temperature.
53
Use HKR specification sheets to determine the HKR avail-
46
able for a given air handler.
41

HKR Installation

37
Follow instructions listed in Installation and Operating Instruc-
tions shipped with the heat kit.

Electrical Supply Wire and MOP

FIRE HAZARD!
To avoid the risk of property damage, personal injury
or fire, use only copper conductors.
4
HEAT KIT NOMINAL kW
5
6
8
10
27
34
39
20
25
30
40
16
20
24
32
13
17
20
27
11
14
17
23
10
13
15
20
9
11
13
18
8
10
12
16
Table 3
HEAT KIT NOMINAL kW
5
6
8
10
25
32
37
19
24
38
38
15
19
22
30
13
16
19
25
11
14
16
22
9
12
14
19
8
11
12
17
8
10
11
15
Table 4
= Temperature Rise
= Heater Kit Actual kW
= Btu per kW
=.96 (230 Supply Volts)
=.92 (220 Supply Volts)
=.87 (208 Supply Volts)
= Constant
= Measured Airflow
15
20
21
48
40
53
59
34
46
51
30
40
44
27
36
39
24
32
35
15
20
21
46
38
51
56
33
43
48
28
38
42
25
34
37
23
30
34