Room temperature limitation

Mixing valve control

Mixing valve decrease
92/221
Siemens Switzerland Ltd
HVAC Products
slight increase of the room temperature causes an immediate drop of the flow
temperature.
To activate the function, following must be considered:
A room sensor must be connected
"Room influence" must be set to 100%
There should be no controlled valves in the reference room (mounting location of
the room sensor) (If such valves are installed, they must be set to their fully open
position)
Line no.
Operating line
932
Room temp limitation
The "Room temperature limitation" function makes it possible to deactivate the cooling
circuit pump if the room temperature falls by more than the preset difference below the
effective room temperature setpoint (with summer compensation, 920).
The cooling circuit pump is activated again as soon as the room temperature returns to
a level above the current room temperature setpoint.
During the time the "Room temperature limitation" function is active, no cooling request
is sent to the source.
The function is deactivated in the following situations:
No room temperature sensor
"Room temp limitation" = ---
"Room influence" (928) = --- (pure weather compensation)
°C
TRx
ON
P
OFF
Line no.
Operating line
938
Mixing valve decrease
939
Actuator type
2-position ¦
3-position
940
Switching differential
2-pos
941
Actuator running time
945
Mixing valve in heating mode
Control ¦
Open
The refrigeration request from the mixing valve circuit to the source is reduced by the
preset value. The purpose of this reduction is to enable the mixing valve controller to
compensate for the variation in temperature caused by the source (2-position control).
User manual RVS61.843
6 The settings in detail
TRx
Actual room temperature
TRKw
Room temperature setpoint cooling
TRKw
TRKw-SDR
compensation)
SDR
Room's switching differential
P
Pump
t
Time
(incl. summer
CE1U2355en_02
23. November 2007